Vemmio DS-100 Manual Download Page 5

 
 

Meter Value 1 = 0x00 (W) 
Meter Value 2 = 0x00 (W) 
Meter Value 3 = 0x03 (W) 
Meter Value 4 = 0xEA (W) 
Meter(W) = Meter Value 3 *256 + Meter Value 4 = 100.2W 

 
2-2-2 Accumulated Power Consumption (KW/h) 

When  receiving  Meter  Get  Command,  it  will  report  Meter  Report 

Command to the node asked. 

         

Meter Get Command:   
[Command Class Meter, Meter Get, Scale = 0x00 KW/h)]

 

 

Meter Report Command:   

[Command Class Meter

Meter Report

Rate Type = 0x01

, 

Meter Type 

=0x01

, 

Precision = 2

Scale = 0x00

Size = 4

Meter Value (KWh)] 

 
          Example: 
          Scale = 0x00 (KWh) 
          Precision = 2 
          Size = 4 Bytes (KW/h) 
          Meter Value 1 = 0x00(KWh) 
          Meter Value 2 = 0x01(KWh) 
          Meter Value 3 = 0x38(KWh) 
          Meter Value 4 = 0xA3(KWh) 
 
          Accumulated  power  consumption  (KW/h)  =  (Meter  Value  2*65536)  + 

(Meter Value 3*256) + (Meter Value 4) = 800.35 (KW/h) 

 
2-2-3 Clearing accumulated power consumption 

      Whenever re-start counting the accumulated power consumption is needed, 

you can use Meter Reset Command to clear it. 

 

Meter Reset Command: [Command Class Meter, Meter Reset]

 

 
2-2-4 AC load Voltage (V) 
        When receiving Meter Get Command, it will report Meter Report Command 

to the node asked. 
 

Meter Get Command: [Command Class Meter, Meter Get, Scale =0x04(V)] 

 

Meter Report Command: 

[Command Class Meter

Meter Report

Rate Type = 0x01

Meter Type = 

0x01

Precision = 1

Scale = 0x04

Size = 2

, 

Meter Value(V)] 

 
Example: 
Scale = 0x04 (V) 
Precision = 1   
Size = 2 (2 Bytes of    V) 
Meter Value 1 =    0x09(V) 
Meter Value 2 =    0x01(V) 
AC load Voltage =    (Meter Value 1*256) +(Meter Value 2)= 230.5 (V) 
 
2-2-5 AC load current ( I ) 
When  receiving  Meter  Get  Command,  it  will  report  Meter  Report  Command  to 
the node asked.

 

 

Meter Get Command: [Command Class Meter, Meter Get, Scale =0x05(I)] 

 

Meter Report Command: 

[Command Class Meter

Meter Report

Rate Type = 0x01

Meter Type 

= 0x01

Precision = 2

Scale = 0x05

Size = 2

Meter Value(I)] 

 
Example: 
Scale = 0x05 (I) 
Precision = 2   
Size = 2 (2 Bytes of I) 
Meter Value 1 =    0x01(I) 
Meter Value 2 =    0x21(I) 
AC load current =    (Meter Value 1*256) +(Meter Value 2)= 2.89 (A) 
 
2-2-6 load power factor (PF) 
When  receiving  Meter  Get  Command,  it  will  report  Meter  Report  Command  to 

Summary of Contents for DS-100

Page 1: ...etecting overload state the Module will be disabled and its On Off button will be lockout of which LED will flash quickly However disconnect and re connect the Module will reset its overload condition...

Page 2: ...Controller means inclusion Removing a node ID allocated by Z Wave Controller means exclusion Failed or success in including excluding the node ID can be viewed from the Z Wave Controller Sometimes pe...

Page 3: ...port ON when relay 2 ON Report OFF when relay 2 OFF Configuration parameter 3 3 default Report ON when either relay 1 ON or relay 2 ON Report OFF when both relay 1 and relay 2 OFF Basic Get Command Co...

Page 4: ...3 Binary Switch Report ON Command Class Switch Binary Switch Binary Report Value 255 0xFF OFF Command Class Switch Binary Switch Binary Report Value 0 0x00 2 1 2 Instant Power Consumption vary over 5...

Page 5: ...it Meter Reset Command Command Class Meter Meter Reset 2 2 4 AC load Voltage V When receiving Meter Get Command it will report Meter Report Command to the node asked Meter Get Command Command Class Me...

Page 6: ...int set to 3 DS 100 will reply ON 0xFF when either Relay 1 or Relay2 is ON report OFF 0x00 when both Relay 1 and Relay2 are OFF Below is an example show a source endpoint 5 send a Get command to DS 10...

Page 7: ...value will be 0 Bit Address Destination End Point 0x01 Bit Address 0 Destination End Point range1 3 Command Class 0x25 Command_Class_Switch_Binary 0x25 Command 0x01 Switch_Binary_Set 0x01 Parameter 1...

Page 8: ...l this value will be 0 Bit Address Destination End Point 0x01 Bit Address 0 Destination End Point range1 3 Command Class 0x32 Command_Class_Meter_V3 0x32 Command 0x05 Meter_Reset 0x05 2 3 5 METER_GET...

Page 9: ...rce End Point 0x05 this is the endpoint of command inquirer here we assume endpoint is 5 if the inquirer doesn t support multi Channel this value will be 0 Bit Address Destination End Point 0x03 Bit A...

Page 10: ...Scale V 0x04 DS 100 AC load Voltage report example COMMAND_CLASS_MULTI_CHANNEL MULTI_CHANNEL_CMD_ENCAP Source End Point 0x03 Meter report Endpoint3 Bit Address Destination End Point 0x05 Bit Address 0...

Page 11: ...02 Parameter 1 0xA1 Scale Bit2 1 Rate Type 0x01 Meter Type 0x01 Parameter 2 0x4A Precision 2 Scale Bit1Bit0 0x01 Size 2 Parameter 3 0x00 Current 0x002B 0 43A Parameter 4 0x2B 2 3 5 5 Get power factor...

Page 12: ...0 7 Restore switch state mode 1 0 2 1 0 Switch off 1 Last switch state 2 Switch on 8 Auto off timer 2 0 0x7FFF 1s 0 0 Disable auto off function 1 0x7FFF 1s 32767s 9 RF off command mode 1 0 3 0 0 Switc...

Page 13: ...same position correspond to same state of relay1 and relay2 if the DS 100 relay change the state because of receiving Z Wave RF command it may need two times of change switch on to off or switch off...

Page 14: ...Endpoint3 is dynamic 4 Protection Command Classes DS 100 supports Protection Command Class version 2 it can protect the switch against unintentionally control by e g a child And it can also protect t...

Page 15: ...environment or human health from uncontrolled waste disposal recycle it responsibly to promote the sustainable reuse of material resources To return your used device please use the return and collect...

Page 16: ...armful interference and 2 This device must accept any interference received including interference that may cause undesired operation FCC Caution Any changes or modifications not expressly approved by...

Reviews: