JK Thermocouples
Type of sensor
Display message
J
J
K (*)
C (*)
L
L
T
t
E
E
N
n
R
r
S
S
*
The instrument is set to this parameter by default.
(23) this parameter is visible in NTC models only
(24) this parameter is visible in TC models only
[SYS] system menu
Notes:
(25) the password is enabled if the parameter is different from 000
(26) if set to "no", it is not possible to modify all the other parameters,
only to display hem
(27) the following operating modes are available:
0 channels 1 and 2 in direct
mode with set-point 1 and 1
(hysteresis to the right of the set point)
1 channels 1 and 2 in reverse
with set-point 1 and differential 1
(hysteresis to the left of the set point)
2 neutral zone
with channel 1 in reverse and channel 2 in direct with
set-point 1 and differential 1
3
as mode 0 but with differential centred on the set-point
4
as mode 1 but with differential centred on the set-point
5 PWM regulation
with channel 1 in reverse and channel 2 in direct
with set-point 1 and differential 1, and neutral zone where applicable
6
switching between outputs in direct (with set-point 1 and differential 1)
and outputs in reverse (with set-point 2 and differential 2) from digital input
7
outputs in direct with switching between set-point 1/differential 1 and
set-point 2/differential 2 from digital input
Labels of
parameters that
can be modified
Description
Parameter
values
default notes
PS1
password 1
-
0
255
0
(25)
PS2
password 2
-
0
255
0
(25)
NEN
Parameter modification enable
-
yes
no
yes
(26)
PRO
Operating mode
-
0
12
0
(27)
min max
unit
En