important information
Please read instructions carefully before proceeding and keep them for future
reference on the inside of the control system door.
safety
•
Control systems KFX 110/120 are intended for use by persons with the relative
experience and knowledge and who have been given instruction concerning use of
the product by a person responsible for their safety.
•
The installer must instruct the owner in the function of the control system includ-
ing resetting of alarms and position of data plate and instructions.
•
The data plate is placed on the inside of the door of the control system.
•
Children must not be allowed to play with the control system.
•
When resetting alarms, be sure not to touch conductive parts.
•
When resetting alarms, make sure that no body parts can get caught in the win-
dow when reactivated.
product
•
The control system has been designed for use with genuine VELUX products. Con-
nection to other products may cause damage or malfunction.
•
The control system is in conformity with the provisions of the Low Voltage Direc-
tive and the EMC directive for use in household, trade and light industry.
•
When installed, the control system complies with protection degree IP 20.
•
The control system can operate smoke ventilation windows with a total power
consumption of 8 A (KFX 110) and 16 A (KFX 120) respectively.
•
Electrical products and batteries must be disposed of in conformity with national
regulations for electronic waste and not with household waste.
•
The packaging can be disposed of with usual household waste.
installation
•
Installation must be carried out by a certified person in accordance with current
national regulations.
•
The control system must be connected directly to the mains supply in accordance
with national regulations. Ensure that the mains supply cannot be disconnected un-
intentionally. It is recommended that disconnection is only possible using the mains
switch or a key switch. At least one of these means for disconnection must be
incorporated in the fixed wiring in accordance with national wiring requirements.
Maintenance and service
•
Disconnect from mains supply and back-up batteries before carrying out any
maintenance or service work to the smoke ventilation system and ensure that they
cannot be reconnected unintentionally during this time.
•
The smoke ventilation system must be tested after installation, service work and
alterations to the system. It must be inspected by qualified personnel at least once
a year. Tests and inspections must be documented in accordance with national
regulations.
•
During the annual inspection, the scissor support arms of smoke ventilation win-
dow CSP must be checked for grease.
•
If you have any technical questions, please contact your VELUX sales company, see
telephone list or www.velux.com.