GLT-299-7-17 Rev.1 

Jan  24, 2022 

 

 

 

Note: After setting the address, cover the address setting port by using 

the sealing label in order to prevent foreign material from entering the 

product.   

During setting address, the module does not respond to the control 

panel.   

Set the address of module according to Job data. 

 

Subtype Setting 

Set the subtype depending  on the wiring configuration as below. The 

subtype is to be set through the Configurator for the control panel. 

 

Sub 

type 

Input 

Method 

Open 

-circuit 

Detection 

Short 

-circuit 

Detection 

Class 

(Style) 

Interrupt

 

 

Normally 

Open 

Yes 

No 

Class B 

Disabled 

Enabled 

Normally 

Close 

No 

Yes 

Class B 

Disabled 

Enabled 

Normally 

Open 

Yes 

Yes 

Class B 

Disabled 

Enabled 

When interrupt is enabled, it allows a high priority communication to 

the control panel. The consumption current increases with this setting. 

 

Note: Applicable subtype setting differs depending on control panels. 

Subtype 1 to 6 can be used with the control panel complying with UL864 

9

th

 edition. 

Subtype 5 and 6 can be used with the control panel complying with 

UL864 10

th

 edition. 

Please contact Velocity customer service for any required details. 

 

Wiring 

All wiring must conform to applicable local codes, ordinances, and 

regulations. 

Install module wiring in accordance with the appropriate wiring 

diagrams.   

Do not connect cables in reverse polarity. Failure to connect the polarity 
correctly could result in damage to the module and/or other equipment.

CAUTION

!

 

Refer to the figures below for wiring styles. 

Note : All wiring is power-limited and supervised. 

Note: The SLC (signaling line circuit) of VDOT-MiniIP supports Class A 

and Class B wiring, and does not support Class X. 

Class B (Short circuit detection is available) 

EOL (10k ohm) is connected between A+ and A- in VDOT-MiniIP. 

Dry contact is OFF. 

Typical wiring for N/O contacts only

EOL 

10k

Ω

RED (L+)

BLACK (L-)

ORANGE (A+)

GRAY (A-)

Loop

-          +

TO NEXT

DEVICE

-          +

Loop

FROM PANEL OR

PREVIOUS DEVICE

Figure 2 

Class B (Short circuit detection is available) 

EOL (10k ohm) is connected between A+ and A- in VDOT-MiniIP. 

Dry contact is OFF. 

*Two external inputs can be connected to one input line. 

*Resistor of 2.2k ohms

VDOT-RE-2.2k

is an option and not included in 

this product. 

 

 

 

 

 

 

 

 

Figure 3 

 

Normally Close Class B 

Dry contact switch and EOL (10k ohm) are connected in series between 

A+ and A- in VDOT-MiniIP. 

Dry contact is ON. 

*Only one external input can be connected to one input line. 

 

 

 

 

 

 

 

 

Figure 4 

Typical wiring for N/C contacts only

RED (L+)

BLACK (L-)

ORANGE (A+)

GRAY (A-)

EOL 

10k

Ω

Loop

-          +

TO NEXT

DEVICE

-          +

Loop

FROM PANEL OR

PREVIOUS DEVICE

Typical wiring for N/O contacts only

RED (L+)

BLACK (L-)

ORANGE (A+)

GRAY (A-)

EOL 

10k

Ω

2.2k

Ω

2.2k

Ω

Loop

-          +

TO NEXT

DEVICE

-          +

Loop

FROM PANEL OR

PREVIOUS DEVICE

Summary of Contents for VDOT-Mini IP

Page 1: ...s of IDC depending on the Subtype Setting described below Figure 1 Compatibility Requirement To ensure proper operation the module shall be connected to UL listed control panel series Any conventional detector cannot be connected with the module Before Installing Disconnect power to the control panel before installing the module If the module is installed in an existing operational system inform t...

Page 2: ...tall module wiring in accordance with the appropriate wiring diagrams Do not connect cables in reverse polarity Failure to connect the polarity correctly could result in damage to the module and or other equipment CAUTION Refer to the figures below for wiring styles Note All wiring is power limited and supervised Note The SLC signaling line circuit of VDOT MiniIP supports Class A and Class B wirin...

Page 3: ... module goes back to the initial status after the external input is reset on the control panel 5 If subtype is set as 1 and 2 or 5 and 6 open between terminal A and A and confirm that the control panel detects the open circuit If subtype is set as 3 6 short between terminal A and A and confirm that the control panel detects the short circuit FOR WARRANTY SERVICE RETURN TO ZETA ALARMS LIMITED 72 78...

Page 4: ...this had been paid And the warranty period is three 3 years from the shipment from Zeta s factory 1 3 Notwithstanding anything to the contrary in this warranty terms Zeta shall not be liable to the customer by reason of any representation or implied warranty condition or other term or any duty at common law or under the express terms of this warranty terms for any consequential loss or damage whet...

Reviews: