VDOT-ASD-400 Aspiration Detector
Velocity Detection
30
VDOT-ASD-400 Aspirating Smoke Detector User’s Manual V1
All
AL.
OFF
ON
OFF
14 Date & Time YYYY/Year
yy. 2000 2099
2010
It is important that the time and date be set up correctly
on the controller’s internal calendar/clock because it uses
this information to store events in the event log.
ADM
MM/Month NN. 01
12
05
DD/Day
dd. 01
31
18
HH/Hour
HH. 01
23
19
MM/Minute nn. 00
59
36
SS/Second
SS.
00
59
0
15 System
Address
Ad.
1
250
250
Setting the device RS485 address. A device must have a
unique address on the network.
ADM
Factory
Default
dF.
N
Y
N
Setting the function to Y will restore the device to the
factory default settings. However, the device address will
not be affected to prevent from unwanted network error.
DST
Password
PS.
N
Y
Y
When this function is set to Y it requires a password to
enter the Program Mode and has the right to change
settings. Setting this function to N it requires no password
to enter the Program Mode and can only view the
settings.
Reference
Detector
Address
rA.
0
250
0
Setting the reference detector address number between
1 and 250 to enable referencing. When this function is
set to 0 the referencing is disabled.
Reference
Zone
rP.
1
8
1
The zone (detector) number of above reference detector
address.
Reference
Dilution
rd.
1
100
100
The value set with this function is the percentage
reference signal subtracted from the detector’s signal, if a
reference device has been allocated.
Reference
Delay
rt.
0
100
0
This value is the delay time (in seconds) between a build
up of pollution being seen by the reference (if used) and
the pollution being seen by the detector.
16 Log
Smoke Log
Enable
SN.
N
Y
Y
Setting this function to Y enables the smoke/flow log.
There are two selectable log modes, CHANGE and RATE.
On VDOT-ASD-400, 0 is CHAGNGE and 1 is RATE. When
the log mode “CHANGE” is selected the following
change function sets the following change percentage of
the detection full scale: 0.01%, 0.05%, 0.1%, 0.2%, 0.5%,
1%, 2%, 5%
When the log mode “RATE” is selected the following
function sets the following log rate in seconds: 1, 10, 60,
300, 600, 1200, 1800, 3600
Note: For the smoke change, the detection full scale is the
bargraph full scale, which is the same as Fire 1 Level. For
the flow change it’s 200%, the maximum flow reading in
percentage.
ADM
Smoke Log
Mode
SL.
0
1
0
Smoke
Change/Rate
SC.
/St.
0.01/
1
5/
3600
5/
3600
Flow Log
Enable
FN.
N
Y
Y
Flow Log
Mode
FL.
0
1
0
Flow
Chang/Rate
FC.
/Ft.
0.01/
1
5/
3600
5/
3600
17 Scale
Mean Period rt.
15
480
60
This value is the period used to calculate the mean of
smoke background level in this period. The mean period
is selectable between the following values in minute: 15,
60, 12, 240, 480
DST
Sensitivity
Mode 1
S1. 0.1 10.0
1.0
Setting this function to increase or decrease the smoke
detection sensitivity by multiple this value to the original
smoke alarm thresholds when relevant GPI is activated.
This setting must work with the GPI which is set to
Sensitivity Mode 1 or 2. If this function value is set to be
greater than 1.0, the smoke detection becomes more
sensitive. On the other hand, it becomes less sensitive if
this function value is set to less than 1.0.
This function is usually used when different smoke
detection sensitivity is required in certain situations. For
example, in work hours the smoke background level
increases due to all kinds of production activities. It may
be desirable to have lower sensitivity in work hours and
Sensitivity
Mode 2
S2. 0.1 10.0
1.0