HAM263D
00 (10/10/2008)
VELLEMAN
5
1
2
AC in
AC Power input from a 16.5VAC, minimum 1.5A, 50~60Hz transformer. The primary
side of the transformer must be connected to an un-switched receptacle.
The used transformer must comply with the EN61558 standard for European
countries.
3
DC out
Un-sw12VDC output power referring to the common ground. Continues
output, not depending on the arm/disarmed status. Can be used for devices requiring
uninterrupted power supply e.g. smoke detectors, control keypads etc. This output
has a 750mA resettable fuse.
4
GND
Common Ground (-)
5
DC out
Cont12VDC output power under
normal condition
(no alarm). The output is
switched OFF at alarm condition; it has a 2.5A resettable fuse. Suitable for the
connection of satellite siren/strobe light with internal battery.
6
DC out
Cont12V output power under
alarm condition
until the system is disarmed.
The output has a 2.5A resettable fuse. It is mostly suitable for providing power for the
stand alone strobe light or those devices require continuous operation at alarm
condition after the siren timer is reset (e.g. SV/PSL3).
7
DC out
+12V output power under
alarm condition
with the duration depending on the
setting of the alarm timer; it has a 2.5A resettable fuse. Can be used for electronic
siren or alarm bell.
•
The following 4 contacts are dedicated for the connection of one or more
digital keypads, e.g.
HAA263D, HAA85WP… The total number of keypad(s) and key switches however is limited to four.
8
GND
Common Ground (-) for keypad(s)
9
CLK
Clock wire
for keypad(s)
10
Data
Data wire
for keypad(s)
11
DC out
+12V output power common point with a 750mA resettable fuse for keypad(s) and
key switches.
•
The following 5 contacts are for inputs from key switches, e.g. HAA80MK.
12
Part 1 ON/OFF Arm/disarm partition 1: accepts normally open (N.O) momentary switches.
Multiple switches can be connected in parallel.
13
Part 2 ON/OFF Arm/disarm partition 1: accepts normally open (N.O) momentary switches.
Multiple switches can be connected in parallel.
14
Part 1 status
LED indication partition 1: show zone status of partition 1.
15
Part 2 status
LED indication partition 2: show zone status of partition 2.
16
System status LED indication system: show zone status of entire system.
Note that contacts 12 and 13 can be connected together to one key switch to arm or disarm
partition one and two simultaneously.
•
The following 12 contacts are for the connection of sensor inputs e.g. PIR detectors (HAA52N),
magnetic contacts (HAA25, HAA27) panic buttons (HAA60) … They represent zone 1 to 8 and their
common groundings. The zones are End of Line (E.O.L.) monitored by a 2.2K
Ω
resistor.
•
All normally closed (N.C.) contacts are to be wired in series with the E.O.L. resistor, where all
normally open (N.O.) contacts are to be wired in parallel with the E.O.L. resistor.
1. N.C. contact
2. N.O. contact
3. 2.2K
Ω
E.O.L. resistor