Hydraulic & Fuel Filtration Division
VF-71E Filter Housing Installation Instructions
VEL1658R12 0316 PN09-881
www.velcon.com
-2-
Parker Hannifi n Corporation
Hydraulic & Fuel Filtration Division
1210 Garden of the Gods Road
Colorado Springs, CO 80907 USA
CARTRIDGE CHANGE-OUT
1. When the pressure has risen by 20-25 psi over the initial clean pressure, or
when diff erential pressure reaches 25 psid, the cartridge must be changed.
2. Turn the unit off .
3. Vent the housing at the cover, and drain all liquid through the bottom drain.
MAKE CERTAIN THE HOUSING IS COMPLETELY DRAINED BEFORE
REMOVING THE LID.
4. Loosen the band clamp and remove the lid.
5. Remove the old cartridge and install a new one. See the accompanying
fi gure for proper assembly of parts. Use a new rubber washer included with
each cartridge, and tighten the thumb screw until the rubber washer curls
slightly.
6. Clean the cover o-ring and o-ring groove. Lightly lubricate the O-ring with
the fuel or oil it will be used in, and position it on the groove (or head).
7. Replace the cover and fasten the band clamp.
8. Close the bottom drain and restart fl ow. Close the top air vent when the
housing has fi lled.
9. Check all fi ttings and cover for leaks.
REPLACEMENT PARTS
Description of Part
Velcon Part Number
Band Clamp Assembly
025X903
Air Vent
550X002
Top Seal Plate
12-02M
Rubber Gasket
G-0305
Flat Washer
402X046
Lock Washer
402X082
Th
umb Screw
404X101
*Std. Buna-N Lid Gasket
G-1016
*Optional Viton A Lid Gasket
G-1016A
*NOTE: Lid gaskets can be obtained at most O-ring suppliers. Specify size 2-442.