CARTRIDGE CHANGE-OUT

1.  When the pressure has risen by 20-25 psi over the initial clean pressure, or 

when diff erential pressure reaches 25 psid, the cartridge must be changed.

2.  Turn the unit off .

3.  Vent the housing at the cover, and drain all liquid through the bottom drain. 

MAKE CERTAIN THE HOUSING IS COMPLETELY DRAINED BEFORE 
REMOVING THE LID.

4.  Loosen the band clamp and remove the lid.

5.  Remove the old cartridge and install a new one. See the accompanying 

fi gure for proper assembly of parts. Use a new rubber washer included with 
each cartridge, and tighten the thumb screw until the rubber washer curls 
slightly.

6.  Clean the cover o-ring and o-ring groove. Lightly lubricate the O-ring with 

the fuel or oil it will be used in, and position it on the groove (or head).

7.  Replace the cover and fasten the band clamp.

8.  Close the bottom drain and restart fl ow. Close the top air vent when the 

housing has fi lled.

9.  Check all fi ttings and cover for leaks.

REPLACEMENT PARTS

Description of Part 

Velcon Part Number

Band Clamp Assembly 

025X903

Air Vent 

550X002

Top Seal Plate 

12-02M

Rubber Gasket 

G-0305

Flat Washer 

402X046

Lock Washer 

402X082

Th

 umb Screw 

404X101

*Std. Buna-N Lid Gasket 

G-1016

*Optional Viton A Lid Gasket 

G-1016A

*NOTE:  Lid gaskets can be obtained at most O-ring suppliers. Specify size 2-442.