VMB1RYS

 

 

 

Velbus 

 Legen Heirweg 33, BE-9890 Gavere, Belgium 

 tel. +32 9 384 36 11 

 e-mail: [email protected] 

 www.velbus.eu 

PN-VMB1RYS-ed1 

 

ENGLISH  

 
Read and understand this manual and all safety signs before using this appliance. Keep 
this manual for future reference. 

DESCRIPTION 

Mini single-channel changeover relay module (for stand-alone and Velbus operation). 

USAGE AND CONFIGURATION 

The VMB1RYS can be used as a stand-alone changeover relay (with an external input for 
switching  the  relay),  or  as  part  of  a  Velbus  system  (1  relay,  4  virtual  relays,  and  1 
pushbutton channel). 

A. Stand-Alone Mode (factory default) 

By factory default, the VMB1RYS is in stand-alone mode. In stand-alone mode, a button 
connected to the external input directly controls the relay. Select the operation mode 
(toggle or pushbutton) using the MODE/TERM switch on the back (see instructions on 

the module sticker). In “toggle” mode, the external input wi

ll control the relay in an ON-

OFF mode (each time the input is closed, the relay will switch from open to closed and 

vice versa). In “pushbutton” mode, the external input will control the relay in an (ON)

-

OFF mode (only while the input is closed, the relay is closed too, otherwise it remains 
open). 
STATUS LED:

 

 

off: NO open, NC closed 

 

on: NO closed, NC open 

 

3 flashes, pause, 3 flashes, etc.: supply voltage too low 

PS LED: supply voltage detected 
Rx-Tx LED: not applicable 

B. Velbus Mode 

To use the VMB1RYS as part of a Velbus system, connect it to a Velbus bus cable with at 
least one other Velbus module and configure it using the Velbus configuration software 
VelbusLink. (For more information on the Velbus system, go to www.velbus.eu.) By 
changing th

e VMB1RYS’s electronic address from FF(HEX)/255(DEC) to any other valid 

value (01-253 DEC), Velbus mode is activated. In Velbus mode, the external input no 
longer directly controls the relay, but instead both can be configured using the Velbus 
configuration software VelbusLink. In Velbus mode, the MODE/TEMP switch on the back 
selects the position of the CAN bus terminator (open or closed). 
To return the VMB1RYS to standalone mode, reset the electronic address to 
FF(HEX)/255(DEC) using the Velbus configuration software VelbusLink. 
STATUS LED:

 

 

off: NO open, NC closed 

 

on: NO closed, NC open 

 

slow flashing: timer is running 

 

2 flashes, pause, 2 flashes, etc: communication error 

 

3 flashes, pause, 3 flashes, etc.: supply voltage too low 

PS LED: supply voltage detected 
Rx LED: CAN bus package received 
Tx LED: CAN bus package sent 

TECHNICAL SPECIFICATIONS 

Relay max. load: 

 

resistive: 10 A @ 230 VAC / 10 A @ 30 VDC 

 

capacitive: 6 A @ 230 VAC 

 

inductive: 6 A @ 230 VAC 

 

voltage range: 0-250 VAC, 0-30 VDC 

Operating conditions: -10 °C to +55 °C 
Supply voltage: 15 ± 3 VDC 
Max. current consumption: 50 mA 
Dimensions: 37 x 57 x 19 mm (L x W x D) 
Protection rating: IP10 
Number of Velbus channels: 6 (1 relay, 4 virtual relays, 1 external input) 
For a complete list of technical specifications, see the product page at www.velbus.eu. 

CONNECTION DIAGRAMS 

A. Stand-Alone Mode (factory default) 

 

 

B. Velbus Mode 

 

 

 

This product complies with all of the relevant European guidelines and 
regulations. 

 

 

 

This symbol on the device or the package indicates that disposal of the 
device after its lifecycle could harm the environment. Do not dispose of 
the unit (or batteries) as unsorted municipal waste; it should be taken 
to a specialized company for recycling. This device should be returned 
to  your  distributor  or  to  a  local  recycling  service.  Respect  the  local 
environmental rules. 

 

Summary of Contents for VMB1RYS

Page 1: ...van de VMB1RYS te wijzigen van FF HEX 255 DEC naar een andere geldige waarde 01 253 DEC wordt de Velbus modus geactiveerd In Velbus modus stuurt de externe ingang niet langer rechtstreeks het relais aan maar kunnen beide worden geconfigureerd met behulp van de Velbus configuratiesoftware VelbusLink In Velbus modus selecteert de MODE TEMP schakelaar aan de achterkant de positie van de CAN busafslui...

Page 2: ...angeant l adresse électronique du VMB1RYS de FF HEX 255 DEC à toute autre valeur valide 01 253 DEC le mode Velbus est activé En mode Velbus l entrée externe ne contrôle plus directement le relais mais les deux peuvent être configurés à l aide du logiciel de configuration VelbusLink de Velbus En mode Velbus le commutateur MODE TEMP situé à l arrière sélectionne la position de terminaison du bus CAN...

Page 3: ...us eu By changing the VMB1RYS s electronic address from FF HEX 255 DEC to any other valid value 01 253 DEC Velbus mode is activated In Velbus mode the external input no longer directly controls the relay but instead both can be configured using the Velbus configuration software VelbusLink In Velbus mode the MODE TEMP switch on the back selects the position of the CAN bus terminator open or closed ...

Page 4: ...Sie die elektronische Adresse vom VMB1RYS ändern von FF HEX 255 DEC in einen anderen gültigen Wert 01 253 DEC wird der Velbus Modus aktiviert Im Velbus Modus steuert der externe Eingang das Relais nicht mehr direkt an sondern können beide mit der Velbus Konfigurationssoftware VelbusLink konfiguriert werden Im Velbus Modus wählt der MODE TEMP Schalter auf der Rückseite die Position der CAN Bustermi...

Reviews: