Chapter 2 Mechanical Installation
- 15 -
Chapter 2 Mechanical Installation
2.1 Installation Environment
1. Ambient Temperature: The temperature affects the life of product. It is prohibited to run
the product
out of ambient temperature range (-10
℃
~50
℃
).
2. Please install the product on flame retardants and mount it vertically on mounting brackets using blots
or screws. Be sure to allow sufficient space around the inverter for heat dissipation since it generates heat
while running.
3. Please install the inverter on a flat surface where the vibration should remain lower than 0.6g, away
from punches, etc.
4. Avoid installing the inverter under direct sunlight or in humid places.
5. Avoid installing the inverter in places of corrosive, flammable and explosive gas.
6. Avoid installing the inverter in places full of oil, dust and metal particles.
2.2 Installation Space and Directions
2.2.1 Single Inverter Installation: the installation and insulation space for an inverter has to be left out
based on its different power ratings.
2.2.2 Multiple Inverters Installation: Inverters dissipate from bottom to top. Therefore, when multiple
inverters are operating, they are usually installed side by side and aligned to top, especially for different
sizes of inverters.
Power level
Size Requirements
0.75kW-22kW
A
≥
10mm
B
≥
100mm
C
≥
40mm
30kW-37kW
A
≥
50mm
B
≥
200mm
C
≥
40mm
45kW-75kW
A
≥
50mm
B
≥
200mm
C
≥
40mm
90kW-710kW
A
≥
50mm
B
≥
200mm
C
≥
40mm
Power level
Size Requirements
0.75kW-22kW
A
≥
10mm
30kW-37kW
A
≥
50mm
45kW-75kW
A
≥
50mm
90kW-710kW
A
≥
50mm
Power Ratings
0.75KW-22kW
30KW-37kW
Size Requirements
A≥10mm
B≥100mm
A≥50mm
B≥200mm
A≥50mm
B≥200mm
A≥50mm
B≥300mm
45KW-75kW
90KW-710kW
Installation Space Requirements
C≥40mm
C≥40mm
C≥40mm
C≥40mm
0.75kW-22kW
30kW-37kW
A≥10mm
A≥50mm
A≥50mm
A≥50mm
45kW-75kW
90kW-710kW
Hot Air
Cold Air
Installation Space Requirements
Power Ratings Size Requirements
Hot Air
Cold Air