AC310 Series Frequency AC Drive Manual 

33 

F10.15 

(0x0A0F) 

Energy consuming 

braking action voltage 

V/F    SVC    FVC    PMVF    PMSVC    PMFVC   

Set  the  energy  consuming  braking  action  voltage,  when  the bus 
voltage  is  greater  than  this  value,  the  energy  consuming  brake 
starts to act

 

T3

735 

S2

360 

(0~ overvoltage point) 

T3 overvoltage 

point:820V;S2 

overvoltage 

point:390V 

RUN 

F10.16 

(0x0A10) 

Bus undervoltage 

suppression 

V/F    SVC    FVC    PMVF    PMSVC    PMFVC   

When the bus voltage is lower than the undervoltage suppression 
point, the operating frequency is automatically adjusted to suppress 
the bus voltage from decreasing, preventing the undervoltage fault. 
0: off 1: on

 

(0 ~ 1) 

STOP 

F10.17 

(0x0A11) 

Bus undervoltage 
suppression point 

V/F    SVC    FVC    PMVF    PMSVC    PMFVC   

Set bus voltage value for trigger undervoltage suppression function

 

T3

430 

S2

240 

(0~ overvoltage point) 

T3 overvoltage 

point:820V;S2 

overvoltage 

point:390V 

STOP 

F10.18 

(0x0A12) 

Bus undervoltage 

suppression gain 

V/F    SVC    FVC    PMVF    PMSVC    PMFVC   

Set the response effect of undervoltage suppression

 

100.0% 

(0.0

500.0%) 

RUN 

F10.19 

(0x0A13) 

Bus undervoltage 

protection point 

V/F    SVC    FVC    PMVF    PMSVC    PMFVC   

Set the allowable lower limit of the bus voltage. Below this value, the 
AC Drive reports undervoltage fault.

 

T3

350 

S2

190 

(0~ overvoltage point) 

T3 overvoltage 

point:820V;S2 

overvoltage 

point:390V 

STOP 

F10.2x

Auxiliary Protection

 

Parameter 

Address

 

Name 

Content 

Factory default 

(range) 

Adjustable 

properly 

F10.20 

(0x0A14) 

Input and output phase 

loss protection options 

V/F    SVC    FVC    PMVF    PMSVC    PMFVC   

Set whether the input and output phase loss protection functions are 
enabled. 
Unit: Output phase loss protection 
0: off 1: on 
Tens: input phase loss protection 
0: off        1: On, when detect the input loss phase report warning 
A.ILF, continue to run 
2: On, when detect input loss phase report fault E.ILF, free stop 

0021 

(000 ~ 0121) 

STOP 

F10.21 

(0x0A15) 

Input phase loss 

threshold 

V/F    SVC    FVC    PMVF    PMSVC    PMFVC   

Set  the  percentage  of  voltage  detection  of  the  input  phase  loss 
detection function, 100% corresponds to the rated bus voltage 

10% 

(0 ~30.0%) 

STOP 

F10.22 

(0x0A16) 

Ground short circuit 

protection option 

V/F    SVC    FVC    PMVF    PMSVC    PMFVC   

Set  whether  the  AC  Drive  output  and  the  AC  Drive  cooling  fan 
ground short circuit protection function are enabled. 
Unit: Output short circuit protection 
0: off 1: on 
Tens: fan to ground short circuit protection 
0: off 1: on 

0011 

(0000 ~0012) 

STOP 

F10.23 

(0x0A17) 

Fan ON/OFF control 

selection 

V/F    SVC    FVC    PMVF    PMSVC    PMFVC   

Set the AC Drive cooling fan operation mode 
0: The fan runs after the AC Drive is powered on. 
1: After the shutdown, the fan operation is related to temperature, 
and the operation is running. 
2: After the shutdown, the fan stops after F10.24, and the operation 
is related to temperature. 

(0

2) 

RUN 

F10.24 

(0x0A18) 

Fan control delay time 

V/F    SVC    FVC    PMVF    PMSVC    PMFVC   

Set the time from shutdown to the cooling fan stops running

 

30.00s 

(0 ~600.00) 

STOP 

F10.25 

(0x0A19) 

AC Drive overheating 

oH1 warning detection 

level 

V/F    SVC    FVC    PMVF    PMSVC    PMFVC   

Set the temperature value of the AC Drive overheat warning, which 
is highter than the value to report the overheat warning.

 

80.0

 

(0 ~100.0) 

RUN 

 

Summary of Contents for AC310

Page 1: ...5 F02 MOTORPARAMETER 16 4 6 F03 VECTOR CONTROLLING 18 4 7 F04 V FCONTROLLING 21 4 8 F05 INPUTTERMINAL 22 4 9 F06 OUTPUTTERMINAL 25 4 10 F07 OPERATIONALCONTROL 29 4 11 F08 AUXILIARY CONTROL 31 4 12 F0...

Page 2: ...nd confirm that the DCvoltage of the main circuit has dropped to Safety level wait 5 minutesbefore performing related work Thepowercable motor cable andcontrolcable must be tightly connected Theground...

Page 3: ...atic torque boost 0 0 100 0 Manual torqueboost 0 0 30 0 V F curve Four modes linear torque characteristic curve self set V Fcurve torque reduction characteristic curve 1 1 to 2 0 power square V Fcurve...

Page 4: ...192 155 149 65 65 193 5 5 4 3 M4 AC310 T3 1R5G 2R2P B AC310 T3 2R2G B AC310 T3 004G 5R5P B 100 242 231 155 149 84 86 5 231 5 8 5 5 3 M4 AC310 T3 5R5G 7R5P B AC310 T3 7R5G 011P B 116 320 307 5 175 169...

Page 5: ...uirements 150mm 150mm Externalkeyboard shape and opening size Note LCDkeyboard is fully compatible with LED keyboard size and opening size AC310 Series Externalkeyboard pocket shape and opening size L...

Page 6: ...electrical components instructions Name Installation andselection Function Definition DCreactor Installed between the EMC filter and thebraking resistor 132kWand above standard Increase thepowerfactor...

Page 7: ...ard shiftkeyfunction to quicklyselect Runmonitoringstatus view Note When using the external keyboard use the left shift button to cycle through the first line of monitoring parameters and use the righ...

Page 8: ...or usage modenumber 0 0 65535 RUN F00 08 0x0008 Free parameter 2 V F SVC FVC PMVF PMSVC PMFVC Whenusing multiple machines use the machine numberor usage modenumber 0 0 65535 RUN F00 10 F00 3 9 0x0010...

Page 9: ...ation time 3 V F SVC FVC PMVF PMSVC PMFVC Time required for the output frequency to decelerate from the reference frequencyto 0 00 Hz Modelrelated 0 01 650 00s RUN F01 28 0x011C Acceleration time 4 V...

Page 10: ...stator resistance standard value V F SVC FVC PMVF PMSVC PMFVC Setthe stator resistance valueofthe PM Modelrelated READ F02 26 0x021A Synchronousmachine D axis inductance standard value V F SVC FVC PMV...

Page 11: ...esponds to F01 10 maximum frequency 10 0 0 0 100 0 RUN F03 23 0x0317 Asynchronousmotor slip compensation V F SVC FVC PMVF PMSVC PMFVC Setthe asynchronousmotorspeed slip compensation 100 0 0 0 250 0 RU...

Page 12: ...l torque boost 0 0 0 0 30 0 RUN F04 02 0x0402 Torque boostcutoff frequency V F SVC FVC PMVF PMSVC PMFVC Set the effective range of the torque boost function When the output frequency exceeds this valu...

Page 13: ...l X4 transit from the active state to the inactive state 0 010 0 000 6 000s RUN F05 18 0x0512 X5 effective detection delay V F SVC FVC PMVF PMSVC PMFVC The delay time corresponding to the input termin...

Page 14: ...tthe lower limitofcurve 2 0 0 0 0 100 0 RUN F05 71 0x0547 Curve 2 lower limit corresponding setting V F SVC FVC PMVF PMSVC PMFVC Setthe corresponding percentage 0 00 0 00 100 00 RUN F05 72 0x0548 Curv...

Page 15: ...y default range Adjustable properly F06 50 0x0632 Comparator 1 monitor selection V F SVC FVC PMVF PMSVC PMFVC UnitsandTensdigits Set yyvalue ofthe Cxx yy 00 63 Hundredsand thousands Setxxvalue ofthe C...

Page 16: ...0 command isinvalid 1 command isvalid 0000 0000 1121 STOP F07 06 0x0706 Powerfailurerestart action selection V F SVC FVC PMVF PMSVC PMFVC 0 Invalid 1 Valid 0 0 1 STOP F07 07 0x0707 Powerfailurerestar...

Page 17: ...0 Second 1 Minute 2 Hour 0 0 2 STOP F08 08 0x0808 Timersetting V F SVC FVC PMVF PMSVC PMFVC Setthe timersetting 0 0 65000 STOP F08 3x Swing Frequency Control Parameter Address Name Content Factory def...

Page 18: ...and outputphase loss protection options V F SVC FVC PMVF PMSVC PMFVC Setwhether the inputand outputphase lossprotection functionsare enabled Unit Outputphase lossprotection 0 off1 on Tens inputphase l...

Page 19: ...MFVC Setthe waiting time fromfaultto reset 1 0s 0 100 0 STOP F10 52 0x0A34 Number offault recovered V F SVC FVC PMVF PMSVC PMFVC This value indicates the number of self recovery that have been perform...

Page 20: ...cation 0000 0000 FFFF RUN F11 24 0x0B18 Monitoring parameter filtering selection V F SVC FVC PMVF PMSVC PMFVC Unit Outputcurrentdisplayfilter 0 F the largerthe value the deeper the filter 0002 0000 00...

Page 21: ...X A monitoring frame addressgroup 3 V F SVC FVC PMVF PMSVC PMFVC Ditto 0007 0000 0763 RUN F12 56 0x0C38 Expansion portEX A monitoring frame addressgroup 4 V F SVC FVC PMVF PMSVC PMFVC Ditto 0011 0000...

Page 22: ...x0D1E Sleep frequency V F SVC FVC PMVF PMSVC PMFVC Setsleep frequency 10 00Hz 0 00 Max frequency RUN F13 31 0x0D1F Sleep delay V F SVC FVC PMVF PMSVC PMFVC Setthe timeofsleep delay 60 0S 0 0 3600 0S R...

Page 23: ...nning direction ofthissegment compared with the running command 0 same direction 1 reverse Ten digits acceleration anddeceleration time ofthissection 0 Acceleration deceleration time 11 Acceleration d...

Page 24: ...and Revcommandgiven C02 01 0x2301 PIDgiven C02 09 0x2309 Jog commandgiven C02 02 0x2302 PIDoutput C02 60 0x233C Expansion cardAversion C02 03 0x2303 PIDcontrolstatus C02 61 0x233D Expansion card B ve...

Page 25: ...tion Fault A SPD 134 Speed warning Warning E COP 43 Parameter copyfailure Fault A GPS1 135 GPS locked Warning E PG1 44 PGparameter settingerror Fault A GPS2 136 GPS disconnection Warning E PG2 44 Enco...

Page 26: ...o need to replace it please contact the agent where you purchased the product or the salesdepartmentofthe company 5 3 Product Warranty 1 The productduring the warrantyperiod isfaulty Fordetails please...

Page 27: ...erse maximum frequency limit 0x3007 or0x2007 0 1000 correspond to 0 0 100 0 W R Communication given PID set value 0x3008 or0x2008 0 1000 correspond to 0 0 100 0 W R Communication given PID feedback va...

Page 28: ...In thismode the three wireoperation controlterminal Xi isthe stop operation terminal and therunning command isgenerated bythe forward rotation operation terminal X1 forward rotationoperation and the d...

Reviews: