AC310 Series Frequency AC Drive Manual
33
F10.15
(0x0A0F)
Energy consuming
braking action voltage
V/F SVC FVC PMVF PMSVC PMFVC
Set the energy consuming braking action voltage, when the bus
voltage is greater than this value, the energy consuming brake
starts to act
T3
:
735
S2
:
360
(0~ overvoltage point)
T3 overvoltage
point:820V;S2
overvoltage
point:390V
RUN
F10.16
(0x0A10)
Bus undervoltage
suppression
V/F SVC FVC PMVF PMSVC PMFVC
When the bus voltage is lower than the undervoltage suppression
point, the operating frequency is automatically adjusted to suppress
the bus voltage from decreasing, preventing the undervoltage fault.
0: off 1: on
0
(0 ~ 1)
STOP
F10.17
(0x0A11)
Bus undervoltage
suppression point
V/F SVC FVC PMVF PMSVC PMFVC
Set bus voltage value for trigger undervoltage suppression function
T3
:
430
S2
:
240
(0~ overvoltage point)
T3 overvoltage
point:820V;S2
overvoltage
point:390V
STOP
F10.18
(0x0A12)
Bus undervoltage
suppression gain
V/F SVC FVC PMVF PMSVC PMFVC
Set the response effect of undervoltage suppression
100.0%
(0.0
~
500.0%)
RUN
F10.19
(0x0A13)
Bus undervoltage
protection point
V/F SVC FVC PMVF PMSVC PMFVC
Set the allowable lower limit of the bus voltage. Below this value, the
AC Drive reports undervoltage fault.
T3
:
350
S2
:
190
(0~ overvoltage point)
T3 overvoltage
point:820V;S2
overvoltage
point:390V
STOP
F10.2x
:
Auxiliary Protection
Parameter
(
Address
)
Name
Content
Factory default
(range)
Adjustable
properly
F10.20
(0x0A14)
Input and output phase
loss protection options
V/F SVC FVC PMVF PMSVC PMFVC
Set whether the input and output phase loss protection functions are
enabled.
Unit: Output phase loss protection
0: off 1: on
Tens: input phase loss protection
0: off 1: On, when detect the input loss phase report warning
A.ILF, continue to run
2: On, when detect input loss phase report fault E.ILF, free stop
0021
(000 ~ 0121)
STOP
F10.21
(0x0A15)
Input phase loss
threshold
V/F SVC FVC PMVF PMSVC PMFVC
Set the percentage of voltage detection of the input phase loss
detection function, 100% corresponds to the rated bus voltage
10%
(0 ~30.0%)
STOP
F10.22
(0x0A16)
Ground short circuit
protection option
V/F SVC FVC PMVF PMSVC PMFVC
Set whether the AC Drive output and the AC Drive cooling fan
ground short circuit protection function are enabled.
Unit: Output short circuit protection
0: off 1: on
Tens: fan to ground short circuit protection
0: off 1: on
0011
(0000 ~0012)
STOP
F10.23
(0x0A17)
Fan ON/OFF control
selection
V/F SVC FVC PMVF PMSVC PMFVC
Set the AC Drive cooling fan operation mode
0: The fan runs after the AC Drive is powered on.
1: After the shutdown, the fan operation is related to temperature,
and the operation is running.
2: After the shutdown, the fan stops after F10.24, and the operation
is related to temperature.
1
(0
~
2)
RUN
F10.24
(0x0A18)
Fan control delay time
V/F SVC FVC PMVF PMSVC PMFVC
Set the time from shutdown to the cooling fan stops running
30.00s
(0 ~600.00)
STOP
F10.25
(0x0A19)
AC Drive overheating
oH1 warning detection
level
V/F SVC FVC PMVF PMSVC PMFVC
Set the temperature value of the AC Drive overheat warning, which
is highter than the value to report the overheat warning.
80.0
℃
(0 ~100.0)
RUN