AC310 Series Frequency AC Drive Manual
29
4.10
F07
:
Operational Control
Parameter
(
Address
)
Name
Content
Factory default
(range)
Adjustable
properly
F07.00
(0x0700)
Start mode
V/F SVC FVC PMVF PMSVC PMFVC
0: started by the start frequency
1: DC braking first starts again from the starting frequency
2: Start after the speed tracking and direction judgment
0
(0 ~ 2)
STOP
F07.01
(0x0701)
Start pre-excitation
time
V/F SVC FVC PMVF PMSVC PMFV
Only asynchronous machine vector control (without PG) supports
pre-excitation, other ignore
0.00s
(0.00
~
60.00s)
STOP
F07.02
(0x0702)
Starting frequency
V/F SVC FVC PMVF PMSVC PMFVC
When the given frequency is less than this value, it does not start
and is in standby state
0.50Hz
(0.00
~
upper limit
frequency setting)
STOP
F07.03
(0x0703)
Start protection
selection
V/F SVC FVC PMVF PMSVC PMFVC
0: off 1: on
Unit: terminal start protection when exiting abnormal
Tens: Jog terminal start protection when exiting abnormal
Hundreds: terminal start protection when the command channel is
switched to the terminal
Note: When the free stop, emergency stop, and forced stop
commands are valid, the terminal start protection is enabled by
default, and the protection time is reported as A.RUNx warning.
0111
(0000
~
1111)
STOP
F07.05
(0x0705)
Direction of rotation
V/F SVC FVC PMVF PMSVC PMFVC
Unit: running direction
0
:
Direction unchanged 1
:
Direction reversed
Tens
:
running direction selection
0
:
allow Fwd and Rev commands 1
:
Fwd command only
2
:
Rev command only
Hundreds
:
Frequency control command
0
:
command is invalid 1
:
command is valid
0000
(0000
~
1121)
STOP
F07.06
(0x0706)
Power failure restart
action selection
V/F SVC FVC PMVF PMSVC PMFVC
0
:
Invalid 1
:
Valid
0
(0 ~ 1)
STOP
F07.07
(0x0707)
Power failure restart
waiting time
V/F SVC FVC PMVF PMSVC PMFVC
Set the power failure restart waiting time
0.50s
(0.00
~
60.00s)
STOP
F07.1x
:
Stop Control
Parameter
(
Address
)
Name
Content
Factory default
(range)
Adjustable
properly
F07.10
(0x070A)
Stop mode
V/F SVC FVC PMVF PMSVC PMFVC
0: Deceleration stop 1: Free stop
0
(0 ~ 1)
RUN
F07.11
(0x070B)
Shutdown detection
frequency
V/F SVC FVC PMVF PMSVC PMFVC
When decelerating to stop, when the AC Drive output frequency is
less than this value, it will enter the stop state.
0.50Hz
(0.00
~
upper limit
frequency setting)
RUN
F07.12
(0x070C)
Stop and restart limit
time
V/F SVC FVC PMVF PMSVC PMFVC
Waiting time after restarting after shutdown
0.00s
(0.00
~
60.00s)
STOP
F07.15
(0x070F)
Insufficient lower limit
frequency action
selection
V/F SVC FVC PMVF PMSVC PMFVC
0 : Run according to frequency command
1 : Free running stops, enters the pause state
2 : Run at the following limited frequency 3 : Zero speed operation
0
(0
~
3)
RUN
F07.16
(0x0710)
Zero speed torque
retention factor
V/F SVC FVC PMVF PMSVC PMFVC
Set zero speed torque current, 100.0% corresponds to AC Drive
rated current
60.0%
(0.0
~
150.0%)
RUN
F07.17
(0x0711)
Zero speed torque
holding time
V/F SVC FVC PMVF PMSVC PMFVC
Set zero speed torque hold time
0.0s
(0.0
~
6000.0s)
RUN
F07.18
(0x0712)
Positive reversal dead
time
V/F SVC FVC PMVF PMSVC PMFVC
Fwd and Rev switching, zero frequency maintenance time
0.0s
(0.0
~
120.0s)
STOP
F07.2x
:
DC Breaking and Speed Tracking
Parameter
(
Address
)
Name
Content
Factory default
(range)
Adjustable
properly