AC200 Frequency Inverter Maunal

 

 

26

F4.34-F4.37 

Reserved 

 

 

0x422 

Motor Parameter Group

 

NO. 

Function description 

Range of settings and definition 

Factory 

default 

Feature 

Address 

F5.00 

Motor mode 

0: Asynchronous motors (AM) 

1: Permanent magnet synchronous 

motors (PM) 

× 

0x500 

F5.01 

Number of motor poles 

2

98 

 

0x501 

F5.02 

Motor rated power 

0.1kW

1000.0kW 

Model set 

 

0x502 

F5.03 

Motor rated frequency 

0.01Hz

max frequency 

Model set 

 

0x503 

F5.04 

Motor rated speed 

1rpm

65000rpm 

Model set 

 

0x504 

F5.05 

Motor rated voltage 

1V

1500V 

Model set 

 

0x505 

F5.06 

Motor rated current 

0.1A

3000.0A 

Model set 

 

0x506 

F5.07 

Asynchronous motor 

no-load current 

0.1A

3000.0A 

Model set 

 

0x507 

F5.08 

Asynchronous motor 

stator resistance 

0.01%

50.00% 

Model set 

 

0x508 

F5.09 

Asynchronous motor rotor 

resistance 

0.01%

50.00% 

Model set 

 

0x509 

F5.10 

Asynchronous motor 

stator leakage inductance 

0.01%

50.00% 

Model set 

 

0x50A 

F5.11 

Asynchronous motor 

stator inductance 

0.1%

2000.0% 

Model set 

 

0x50B 

F5.12 

synchronous motor stator 

resistance 

0.01%

50.00% 

Model set 

 

0x50C 

F5.13 

Synchronous machine d 

axis inductance 

0.01%

200.00% 

Model set 

 

0x50D 

F5.14 

Synchronous machine q 

axis inductance 

0.01%

200.00% 

Model set 

 

0x50E 

F5.15 

Synchronous machine 

back EMF 

1V

1500V 

Model set 

 

0x50F 

F5.16 

Synchronous machine 

encoder installation angle 

0.0°

360.0° 

Model set 

 

0x510 

F5.17-F5.19 

Reserved 

 

 

0x511 

F5.20 

Motor parameters 

self-adjustment selections 

0: No operation 

1: Rotary type self-study 

2: Static type self-study 

3: Reserved 

 

0x514 

F5.21 

Synchronous machine 

poles searching function 

LED “0” digit: closed-loop vector 

0: OFF 

1: ON 

2: On, only operate firstly when   

    electrify 

LED “00” digit: open-loop vector 

0010 

 

0x515 

Summary of Contents for AC200 Series

Page 1: ...MANUAL AC200 Series Frequency Inverter...

Page 2: ...2 Installation 5 Chapter 3 Keyboard layout and functions specification 11 Chapter 4 Function Parameter Table 13 4 1 Basic parameters 13 4 2 Terminal Input and Output Function Selection 42 4 3 Monitor...

Page 3: ...by the regulations or requirements in this manual there is danger of body injury even death and machine system damage Do not wire while the power is connected Otherwise there is danger of death for el...

Page 4: ...16 10 200 660 380 218 132 5 5 20 13 220 720 415 235 144 7 5 30 17 10 250 470 270 162 11 42 25 15 280 510 330 175 15 55 32 18 315 600 345 208 18 5 70 38 22 355 670 380 220 22 80 45 28 400 750 430 260 3...

Page 5: ...e capacity Auto torque upgrade 0 0 100 0 Manual torque upgrade 0 0 30 0 V F curve 4 modes one linearity torque characteristic curve one user setting V F curve mode one drop torque characteristic curve...

Page 6: ...lay overheat overvoltage stall data protection rapid speed protection input output loss phase protection Keyboard display LED display Single file 5 digital tube display Can monitor one state variable...

Page 7: ...D1 D MODEL W W1 H H1 D D1 INSTALLATION APERTURE AC200 S2 R40G 122 112 182 171 154 5 145 5 AC200 S2 R75G AC200 S2 1R5G AC200 S2 2R2G 159 147 2 246 236 157 5 148 5 5 AC200 T3 R75G 122 112 182 171 154 5...

Page 8: ...AC200 T3 030G 255 410 225 370 180 395 7 AC200 T3 037G 305 570 260 522 180 550 9 AC200 T3 045G AC200 T3 055G AC200 T3 075G 380 620 290 564 240 595 11 AC200 T3 090G AC200 T3 110G H1 H H2 D W1 W MODEL O...

Page 9: ...80 450 1150 550 1236 20 AC200 T3 355G AC200 T3 400G D1 W 1 D W H H1 MODEL Overall Dimension Instillation Position INSTALLATION APERTURE W H D H1 W1 D1 AC200 T3 160GD 650 1600 400 1500 492 332 14 AC200...

Page 10: ...n Instillation Position INSTALLATION APERTURE W H D H1 W1 D1 AC200 T3 450G 1200 1850 550 1750 960 466 14 AC200 T3 500G AC200 T3 560G MODEL Overall Dimension Instillation Position INSTALLATION APERTURE...

Page 11: ...nd resistor low than 10 W V U output reactor DC reactor brake resistor short circuit P1 R brake module voltage model analog input current model analog input 10V R T S AC input AI GND AS VS shielded tw...

Page 12: ...Function Specification S1 K1 AO1 0 mA 20mA or 4 mA 20mA current output K2 AO1 0V 10V voltage output S2 K3 AI 0 mA 20mA or 4 mA 20mA input current K4 AI 0V 10V input voltage S3 K5 AO2 0 0 kHz 100kHz J...

Page 13: ...PID are set by keyboard and F4 09 needs to be set Shift key Select digit of function No modified by up down key Select parameter digits modified by up down key Forward run key While run stop is contr...

Page 14: ...PM On Motor speed unit Spark On Percent unit State indicator light FWD On Forward running FWD Spark Reverse running FWD Off Stop Function indicator light REV JOG On Jog REV JOG Off Reverse Basic LED o...

Page 15: ...mance VC with PG Synchronous motor control mode 6 High performance VC without PG 7 VC with PG Other control 8 Voltage frequency separation output 1 2 5 Reserved 0 0x000 F0 01 Reserved 0x001 F0 02 Run...

Page 16: ...UL given 7 RS485 communication given 8 Terminal UP DW control 9 PID control given A Program control PLC given B Optional card C Multi speed given 0000 0x007 F0 08 Keyboard number setting frequency 0Hz...

Page 17: ...restoring motor parameters 2 Restore factory default restoring motor parameters 3 Clear malfunction records 0 0x013 Run control parameters NO Function description Range of settings and definition Fact...

Page 18: ...0x111 F1 18 ACC finish S curve time 0 00s 10 00s 0 10s 0x112 F1 19 DEC start S curve time 0 00s 10 00s 0 10s 0x113 F1 20 DEC finish S curve time 0 00s 10 00s 0 10s 0x114 F1 21 ACC time 2 0 01s 650 00s...

Page 19: ...lection Table 1 0x200 F2 01 Multifunction input terminal 2 X2 2 0x201 F2 02 Multifunction input terminal 3 X3 4 0x202 F2 03 Multifunction input terminal 4 X4 5 0x203 F2 04 Multifunction input terminal...

Page 20: ...nal operate protection when abnormal exit LED 00 digit Jog terminal operate protection when abnormal exit LED 000 digit Operate protection when command channel switched to terminal LED 0000 digit rese...

Page 21: ...1 Output frequency level 1 FDT1 0 00Hz Max frequency 30 00Hz 0x233 F2 52 FDT1 lag 0 00Hz Max frequency 1 00Hz 0x234 F2 53 Output frequency level 2 FDT2 0 00Hz Max frequency 50 00Hz 0x235 F2 54 FDT2 la...

Page 22: ...as X See X terminal function 0 0x314 F3 21 VS high level setting 0 00 100 00 70 00 0x315 F3 22 VS low level setting 0 00 100 00 30 00 0x316 F3 23 AI terminal function selection used as X See X termina...

Page 23: ...0V 10 00V 0 00V 0x328 F3 41 Curve 2 lower limit corresponding setting 0 00 100 00 0 00 0x329 F3 42 Curve 2 inflection point 1 input voltage 0 00V 10 00V 3 00V 0x32A F3 43 Curve 2 inflection point1 cor...

Page 24: ...ature 1 17 Module temperature 2 18 RS485 given 0 0x336 F3 55 A02 output selection 1 0x337 F3 56 A01 output gain 25 0 200 0 100 0 0x338 F3 57 A01 output signal bias 10 0 10 0 0 0 0x339 F3 58 A01 output...

Page 25: ...arameters to inverter Remaining value no operation 0 0x405 F4 06 Keyboard special function selection LED 0 digit D E monitor on 0 Off 1 On LED 00 digit no keyboard potentiometer lock sampling value 0...

Page 26: ...group 00 63 LED 000 and 0000 digit display the second group 00 63 1101 0x40E F4 15 The display content of the first line in running state Same as above 0402 0x40F F4 16 The display content of the firs...

Page 27: ...fter power on the fan runs 1 Stop associated with temperature running is rotary 2 Running associated with temperature stop while the fan stops 1 0x41C F4 29 Dynamic braking enabled 0 Off 1 On 0 0x41D...

Page 28: ...set 0x508 F5 09 Asynchronous motor rotor resistance 0 01 50 00 Model set 0x509 F5 10 Asynchronous motor stator leakage inductance 0 01 50 00 Model set 0x50A F5 11 Asynchronous motor stator inductance...

Page 29: ...r filter of encoder speed inspection 0 0ms 100 0ms 1 0ms 0x524 F5 37 F5 49 Reserved Motor VC Parameter Group NO Function description Range of settings and definition Factory default Feature Address F6...

Page 30: ...effective range 0 0 100 0 10 0 0x615 F6 22 Over excitation braking gain 0 0 500 0 100 0 0x616 F6 23 Over excitation braking amplitude limit 0 0 250 0 100 0 0x617 F6 24 Vector control energy saving fun...

Page 31: ...rque keyboard number setting 0 100 0 0 0 0x702 F7 03 Torque input lower limit 0 00 100 00 0 00 0x703 F7 04 Lower limit corresponding setting 200 00 200 00 0 00 0x704 F7 05 Torque input upper limit 0 1...

Page 32: ...3 0 0x801 F8 02 Self setting frequency F1 0 00Hz max frequency 1 00Hz 0x802 F8 03 Self setting voltage V2 0 0 100 0 28 0 0x803 F8 04 Self setting frequency F2 0 00Hz max frequency 10 00Hz 0x804 F8 05...

Page 33: ...E F8 31 Output voltage of voltage frequency separation number setting 0 0 100 0 0 0 0x81F F8 32 Output voltage of voltage frequency separation ACC time 0 0s 100 00s 10 00s 0x820 F8 33 Output voltage o...

Page 34: ...digit Over voltage suppression control 0 Prohibited 1 Valid in DEC 2 Valid both in ACC DEC LED 00 digit Over excitation control 0 Off 1 On LED 000 digit Reserved LED 0000 digit Reserved 0012 0xA06 FA...

Page 35: ...protection 1 0 Not detected 1 Detected load is too large 2 Detected load is too large only at constant speed 3 Insufficient load detected 4 Insufficient load only at constant speed LED 00 digit Alarm...

Page 36: ...A17 FA 24 detection threshold when speed slip is too large 0 0 60 0 10 0 0xA18 FA 25 detection time when speed slip is too large 0 0s 60 0s 2 0s 0xA19 FA 26 Stall protection action LED 0 digit Detecti...

Page 37: ...ction input terminal status See input terminal chart 0xA2F FA 48 Malfunction output terminal status See output terminal chart 0xA30 FA 49 The last malfunction types Please see malfunction code table 0...

Page 38: ...age analog given 3 Terminal AI voltage and current analog given 4 Terminal AS current analog given 5 Terminal pulse PUL given 6 RS485 communication given 7 Optional card 8 Terminal selection 0 0xB00 F...

Page 39: ...ime I2 0 0s 600 0s 1 0s 0xB0F Fb 16 Differential gain D2 0 000s 6 000s 0 000s 0xB10 Fb 17 PID parameter switching condition 0 No switch 1 Use DI terminal to switch 2 Switch according to deviation 0 0x...

Page 40: ...7 0 00Hz Max frequency 30 00Hz 0xC06 FC 23 PLC Speed 8 0 00Hz Max frequency 20 00Hz 0xC07 FC 08 PLC Speed 9 0 00Hz Max frequency 10 00Hz 0xC08 FC 09 PLC Speed 10 0 00Hz Max frequency 20 00Hz 0xC09 FC...

Page 41: ...0xC1B FC 28 PLC 13th Step running time 0 0 s m h 6500 0 s m h 10 0 0xC1C FC 29 PLC 14th Step running time 0 0 s m h 6500 0 s m h 10 0 0xC1D FC 30 PLC 15th Step running time 0 0 s m h 6500 0 s m h 10 0...

Page 42: ...tion 0 Slave machine 1 Main machine LED 00 digit reserved LED 000 digit reserved LED 0000 digit reserved 0000 0xD00 Fd 01 485 communication address 1 247 1 0xD01 Fd 02 Communication baud rate selectio...

Page 43: ...n command 2 Main machine given frequency 3 Main machine output frequency 4 Main machine upper limit frequency 5 Main machine given torque 6 Main machine output torque 7 Torque control FWD speed limit...

Page 44: ...ency input 60 Speed torque control switch 13 Switch channel A to channel B 36 Swing frequency pause 61 Position control switch 14 channel combination switch to A 37 Swing frequency reset No Definition...

Page 45: ...C 15 Output terminal Y on state See output terminal diagram 210FH C 16 Analog VS input value 0 001V 2110H C 17 Analog AI input value 0 001V 0 001mA 2111H C 18 Analog AS input value 0 001mA 2112H C 19...

Page 46: ...s phase 14 Output side loss phase 15 Rectifier overheat 16 Inverter overheat 17 External fault 18 74 RS485 communica tion abnormal 19 Current detection fault 20 Motor detection fault 21 69 Storage fau...

Page 47: ...c connection and lubricate the machine components Load Check whether output current is over the rated value of the motor or the inverter and has lasted for a period Make sure whether it overload and w...

Page 48: ...ge damaged component Motor Check if there is abnormal vibration or noise Tighten machine and electric connection and lubricate the machine components 5 2 Maintenance All equipments and components have...

Page 49: ...ameter Group Address Specification Function Specification Address Definition Data Meaning Specification R W Characteristic Communication Given Frequency 0x3000 or 0x2000 0 32000 is corresponding to 0...

Page 50: ...0 corresponds output 0V 10V 0mA 20mA R AO2 output 0x3022 or 0x2022 0 10000 corresponds output 0V 10V 0mA 20mA 0kHz 50kHz R Note The other function code addresses refer to Communication Address of func...

Reviews: