24
6 Setup
VEGAWAVE 62 • Two-wire 8/16 mA
32255-EN-181126
16
±1,5
I/mA
8
±1,5
< 3,6
t/s
1
2
3
1,5
±0,5
1,5
±0,5
1,5
±0,5
Fig. 36: Flow chart of the function test (mode "max.")
1 Full signal
2 Empty signal
3 Fault message
Check if all three switching conditions occur in the correct sequence
and the stated time period. If this is not the case, there is a fault in the
measuring system (see also the operating instructions manual of the
signal conditioning instrument). Keep in mind that connected instru-
ments are activated during the function test. By doing this, you can
check the correct function of the measuring system.
Note:
Keep in mind that the starting time t
A
of the voltage supply can extend
the time up to the first switching (e.g. VEGATOR 636: +1 s)
After releasing the button or after a brief line break.
Sensor
current -
Sensor
Level relay
A - overfill
protection
Signal lamp
A - Overfill
protection
Level relay
B - dry run
protection
Signal lamp
B - Dry run
protection
Fail safe
relay
Control
lamp
1. Fault sig-
nal
approx. 1.5
±0.5 s
+ t
A
2)
< 3.6 mA
currentless
currentless
currentless
2. Empty
signal
1.5 s ±0.5 s
8 mA
±1.5 mA
energized
currentless
energized
3. Full signal
1.5 s ±0.5 s
16 mA
±1.5 mA
currentless
energized
energized
Test procedure
2)
Starting time of the voltage supply