20
6 Setup
VEGAVIB 63 • - contactless electronic switch
29278-EN-160122
VEGAVIB 63 will be more sensitive and light solids can be detected
more reliably.
For instruments detecting solids in water, these settings are not
applicable. The switching point adaptation is preset and must not be
changed.
With the mode adjustment (min./max.) you can change the switching
condition of the output. You can set the required mode according to
the "
Function table
" (max. - max. detection or overflow protection, min.
- min. detection or dry run protection).
We recommend connecting according to the idle current principle
(contactless electronic switch is open when the switching point is
reached) because the contactless electronic switch takes on the
same (safe) state if a failure is detected.
Control lamp for indication of the switching status
•
green = switch closed
•
red = switch open
•
red (flashing) = failure
6.3 Function table
The following table provides an overview of the switching conditions
depending on the set mode and the level.
Level
Switching status Control lamp
Mode max.
Overflow protec
-
tion
2
1
Switch closed
Green
Mode max.
Overflow protec
-
tion
2
1
Switch open
Red
Mode min.
Dry run protection
2
1
Switch closed
Green
Mode min.
Dry run protection
2
1
Switch open
Red
Mode adjustment (2)
Signal lamp (5)