4 Connecting to power supply
VEGASON 63 • Four-wire 4 … 20 mA/HART
51864-EN-210616
4 Connecting to power supply
4.1 Connection procedure
Proceed as follows:
1. Unscrew the housing lid
2. Loosen compression nut of the cable gland and remove blind
plug
3. Remove approx. 10 cm (4 in) of the cable mantle (current output),
strip approx. 1 cm (0.4 in) insulation from the ends of the indi
-
vidual wires
4. Insert the cable into the sensor through the cable entry
5. Lift the opening levers of the terminals with a screwdriver
6. Insert the wire ends into the open terminals according to the wir-
ing plan
Fig. 3: Connection steps 5 and 6
7. Press down the opening levers of the terminals, you will hear the
terminal spring closing
8. Check the hold of the wires in the terminals by lightly pulling on
them
9. Connect the shielding to the internal ground terminal, connect the
external ground terminal to potential equalisation
10. Tighten the compression nut of the cable entry gland. The seal
ring must completely encircle the cable
11. Connect the lead cable for power supply in the same way accord-
ing to the wiring plan, in addition connect the ground conductor to
the inner ground terminal.
12. Screw the housing lid back on
The electrical connection is finished.