11
5 Set up with the display and adjustment module PLICSCOM
VEGASON 63 • Four-wire 4 … 20 mA/HART
51864-EN-210616
100%
0%
0,25
m
(9.8
4")
5
m
(196.
9")
2
1
3
Fig. 6: Parameterisation example, Min./max. adjustment
1 Min. level = max. distance (depending on the sensor)
2 Max. level = min. distance (final value of the dead zone, depending on the
sensor)
3 Reference plane
The actual product level during this adjustment is not important,
because the min./max. adjustment is always carried out without
changing the product level. These settings can be made ahead of
time without the instrument having to be installed.
High nozzles or vessel installations, such as e. g. struts or agitators as
well as buildup and weld joints on the vessel walls, cause interfering
reflections which can impair the measurement. A false echo storage
detects and marks these false echoes, so that they are no longer
taken into account for the level measurement. A false echo memory
should be created with low level so that all potential interfering reflec
-
tions will be detected.
False signal suppression
Change now?
Proceed as follows:
1. Move from the measured value display to the main menu by
pushing
[OK]
.
2. Select the menu item "
Service
" with
[->]
and confirm with
[OK]
.
Now the menu item "
False signal suppression
" is displayed.
3. Confirm "
False signal suppression - Change now
" with
[OK]
and
select in the below menu "
Create new
". Enter the actual distance
from the sensor to the medium surface. All false signals in this
area are detected by the sensor and saved after confirming with
[OK]
.
Service - False signal
suppression