9 Diagnosis, Asset Management and service
VEGAPULS WL 61 • 4 … 20 mA/HART - two-wire
38061-EN-121011
The following table shows the error codes and text messages in the
status message "
Failure
" and gives information on the cause and how
to eliminate it. Keep in mind that some specifications are only valid for
four-wire instruments and the electronics of VEGAPULS WL 61 can-
not be exchanged by the user.
Code
Text mes-
sage
Cause
Rectification
F013
no measured
value avail-
able
– Sensor does not detect an
echo during operation
– Antenna system contami-
nated or defective
– Check or correct installation
and/or parameter adjust-
ment
– Clean or exchange process
component or antenna
F017
Adjustment
span too small
– Adjustment not within
specification
– Change adjustment accord-
ing to the limit values (dif-
ference between min. and
max. ≥ 10 mm)
F025
Error in the
linearization
table
– Index markers are not con-
tinuously rising, for examle
unlogical value pairs
– Check linearization table
– Delete table/Create new
F036
No operable
software
– Failed or interrupted soft-
ware update
– Repeat software update
– Check electronics version
– Exchanging the electronics
– Send instrument for repair
F040
Error in the
electronics
– Hardware defect
– Exchanging the electronics
– Send instrument for repair
F080
– General software error
– Separate operating voltage
briefly
F105
Determine
measured
value
– The instrument is still in the
start phase, the measured
value could not yet be
determined
– Wait for the warm-up phase
– Duration depending on
the version and parameter
adjustment up to approxi-
mately 3 min.
F113
Communica-
tion error
– EMC interferences
– Transmission error with the
external communication
with 4-wire power supply
unit
– Remove EMC influences
– Exchange 4-wire power
supply unit or electronics
F125
Unpermissi-
ble electronics
temperature
– Temperature of the elec-
tronics in the non-specified
section
– Check ambient temperature
– Isolate electronics
– Use instrument with higher
temperature range
F260
Error in the
calibration
– Error in the calibration car-
ried out in the factory
– Error in the EEPROM
– Exchanging the electronics
– Send instrument for repair
Failure