6 Set up with the display and adjustment module
VEGAPULS SR 68 • 4 … 20 mA/HART two-wire
38294-EN-130624
If a false signal suppression has already been created in the sensor,
the following menu window appears when selecting "
False signal
suppression
":
The menu item "
Delete
" is used to completely delete an already cre-
ated false signal suppression. This is useful if the saved false signal
suppression no longer matches the metrological conditions in the
vessel.
The menu item "
Extend
" is used to extend an already created false
signal suppression. This is useful if a false signal suppression was
carried out with a too high level and not all false signals could be de-
tected. When selecting "
Extend
", the distance to the product surface
of the created false signal suppression is displayed. This value can
now be changed and the false signal suppression can be extended to
this range.
With the function "
Echo curve memory
" the echo curve can be saved
at the time of setup. This is generally recommended; for using the As-
set Management functions it is absolutely necessary. If possible, the
curve should be saved with a low level in the vessel.
With the adjustment software PACTware and the PC, the high resolu-
tion echo curve can be displayed and used to recognize signal
changes over the operating time. In addition, the echo curve of the
setup can be also displayed in the echo curve window and compared
with the actual echo curve.
A linearization is necessary for all vessels in which the vessel volume
does not increase linearly with the level - e.g. a horizontal cylindri-
cal or spherical tank - and the indication or output of the volume is
required. Corresponding linearization curves are preprogrammed
for these vessels. They represent the correlation between the level
percentage and vessel volume.
By activating the appropriate curve, the volume percentage of the
vessel is displayed correctly. If the volume should not be displayed in
percent but e.g. in l or kg, a scaling can be also set in the menu item
"
Display
".
Diagnostics - Echo curve
memory
Additional adjustments -
Linearization curve