5 Connecting to power supply
VEGAPULS 64 • 4 … 20 mA/HART - two-wire
51141-EN-160815
5
1
2
+
( )
(-)
6 7 8
4...20mA
Display
2
3
4
1
Fig. 29: Terminal compartment, double chamber housing
1 Voltage supply, signal output
2 For display and adjustment module or interface adapter
3 For external display and adjustment unit
4 Ground terminal for connection of the cable screen
Information:
Parallel use of an external display and adjustment unit and a display
and adjustment module in the terminal compartment is not supported.
5.5 Wiring plan - version IP 66/IP 68, 1 bar
1
2
Fig. 30: Wire assignment in permanently connected connection cable
1 brown (+) and blue (-) to power supply or to the processing system
2 Shielding
5.6 Switch-on phase
After connecting the instrument to power supply or after a voltage
recurrence, the instrument carries out a self-check for approx. 30 s:
•
Internal check of the electronics
•
Indication of the instrument type, hardware and software version,
measurement loop name on the display or PC
•
Indication of the status message "
F 105 Determine measured
value
" on the display or PC
•
The output signal jumps to the set fault current
As soon as a plausible measured value is found, the corresponding
current is outputted to the signal cable. The value corresponds to the
actual level as well as the settings already carried out, e.g. factory
setting.
Terminal compartment
Wire assignment, con-
nection cable