T
he following assumptions form the basis for the implemen
-
tation of
FMEDA
:
l
F
ailure rates are constant
,
wear of the mechanical parts is
not taken into account
l
F
ailure rates of external power supplies are not taken into
account
l
M
ultiple errors are not taken into account
l
T
he average ambient temperature during the operating
time is
40
°
C
(
104
°
F
)
l
T
he environmental conditions correspond to an average
industrial environment
l
T
he lifetime of the components is around
8
to
12
years
(
IEC
61508
-
2
,
7
.
4
.
7
.
4
,
remark
3
)
l
T
he repair time
(
exchange of the measuring system
)
after
an nondangerous malfunction is eight hours
(
MTTR
=
8
h
)
l
T
he processing unit can interprete
"
fail low
"
and
"
fail high
"
failures as errors and trigger a suitable error message
l
E
xisting communication interfaces
(
e
.
g
.
HART
,
I
²
C
-
B
us
)
are not used for transmission of safety
-
relevant information
T
he measuring system should be used appropriately taking
pressure
,
temperature
,
density
,
dielectric value and chemical
properties of the medium into account
.
I
nstructions to critical process and vessel situations are
described in the operating instructions manual
.
T
he user
-
speci
fi
c limits must be kept
.
T
he speci
fi
cations of the
operating instructions manual must not be exceeded
.
1
.
3
I
nstrument parameter adjustment
S
ince the plant conditions in
fl
uence the safety of the
measuring system
,
the instrument parameters must be set
according to the application
.
T
he following tools are allowed
:
l
the
DTM
suitable for
VEGAPULS
in conjunction with an
adjustment software according to the
FDT
/
DTM
standard
,
e
.
g
.
PACT
ware
™
l
I
ndicating and adjustment module
N
ote
:
M
ake sure that
DTM
-
C
ollection
10
/
2005
or a newer version is
used
.
A
ssumptions
G
eneral instructions and re
-
strictions
A
djustment tools
VEGAPULS
series
60
-
4
…
20
m
A
/
HART
7
F
unctional safety
31338
-
EN
-
070510
Summary of Contents for VEGAPULS 61
Page 1: ...Safety Manual VEGAPULS series 60 4 20 mA HART Radar...
Page 13: ...VEGAPULS series 60 4 20 mA HART 13 Functional safety 31338 EN 070510...
Page 14: ...14 VEGAPULS series 60 4 20 mA HART Functional safety 31338 EN 070510...
Page 15: ...VEGAPULS series 60 4 20 mA HART 15 Functional safety 31338 EN 070510...