7 Set up with the integrated display and adjustment unit
VEGAPULS 31 • Two-wire 4 … 20 mA/HART
57820-EN-191014
With activated protection of the parameter adjustment, the individual
menu items can be selected and displayed, however the parameters
can no longer be modified.
Releasing the sensor adjustment is also possible in any menu item by
entering the device code.
Note:
The factory set device code is "
000000
". If this is changed by the user
and is no longer available, access is only possible via the emergency
device unlock code on the information sheet "
Emergency unlock
codes
" also supplied.
Caution:
With protected parameter adjustment, adjustment via the VEGA Tools
app as well as PACTware/DTM and other systems is also blocked.
During a reset, parameter settings made by the user are reset to the
values of the basic setting or the delivery status (see chapter "
Menu
overview
")
3)
.
Caution:
For the duration of the reset, the set trouble signal is output via the
current output. Within the context of the asset management function,
the message "
Maintenance
" is output.
The following reset functions are available:
Basic settings:
Resets the parameter settings to the default values
of the respective device. The order-related settings are not transferred
to the current parameters after this reset.
Delivery status:
Resets the parameter settings to the delivery status.
7.4.3 Diagnostics
In this menu item, the device status is displayed.
Reset
Status
3)
Language and Bluetooth access code are not reset.