5
C
onnecting to power supply
5
.
1
P
reparing the connection
A
lways keep in mind the following safety instructions
:
l
C
onnect only in the complete absence of line voltage
l
I
f voltage surges are expected
,
install overvoltage arresters
C
onnect the operating voltage according to the following diagrams
.
T
ake note of the general installation regulations
.
A
s a rule
,
connect
VEGAMIP
61
to vessel ground
(
PA
),
or in case of plastic vessels
,
to
the next ground potential
.
O
n the side of the instrument housing there
is a ground terminal between the cable entries
.
T
his connection serves
to drain o
ff
electrostatic charges
.
I
n
E
x applications
,
the installation
regulations for hazardous areas must be given priority
.
T
he data for power supply are speci
fi
ed in chapter
"
T
echnical data
"
.
T
he instrument is connected with standard two
-
wire cable without
screen
.
I
f electromagnetic interference is expected which is above the
test values of
EN
61326
for industrial areas
,
screened cable should be
used
.
U
se cable with round cross
-
section
.
A
cable outer diameter of
5
…
9
mm
(
0
.
2
…
0
.
35
in
)
ensures the seal e
ff
ect of the cable gland
.
I
f you are
using cable with a di
ff
erent diameter or cross
-
section
,
exchange the
seal or use a suitable cable gland
.
C
over all housing openings conforming to standard according to
EN
60079
-
1
.
5
.
2
C
onnection procedure
T
he voltage supply and signal output are connected via the spring
-
loaded terminals in the housing
.
P
roceed as follows
:
1
U
nscrew the housing cover
2
L
oosen compression nut of the cable entry
3
R
emove approx
.
10
cm
(
4
in
)
of the cable mantle
,
strip approx
.
1
cm
(
0
.
4
in
)
of insulation from the ends of the individual wires
S
afety instructions
V
oltage supply
C
onnection cable
C
onnection technology
C
onnection procedure
VEGAMIP R
61
• -
T
ransistor
23
5
C
onnecting to power supply
40694
-
EN
-
120228