61
15 Supplement
VEGAMET 861 • 4 … 20 mA/HART
58866-EN-200401
Ʋ
Status, fault signal
LED red
Ʋ
Status, operating relay
LED yellow
Background lighting
Colour signalling according to NAMUR NE 107
Adjustment
Adjustment elements
4 x keys for menu adjustment
PC/Notebook
PACTware/DTM
Smartphone/Tablet
VEGA Tools app
Memory card
Memory card type
microSDXC industrial
Capacity (supplied card)
8 GB
Capacitance (max.)
64 GB
Ambient conditions
Ambient temperature
Ʋ
Instrument in general
-40 … +60 °C (-40 … +140 °F)
Ʋ
Display (readability)
-20 … +60 °C (-4 … +140 °F)
Storage and transport temperature
-40 … +80 °C (-40 … +176 °F)
Relative humidity
< 96 %
Electrical protective measures
Protection rating
IP66/IP67 acc. to IEC 60529, Type 4X acc. to UL 50
Altitude above sea level
up to 5000 m (16404 ft)
Overvoltage category (IEC 61010-1)
II
Protection class
I
Pollution degree
4
Protection against dangerous body currents
Reliable separation according to IEC/EN 61140 by reinforced insulation according to IEC/
EN 61010 part 1 up to 253 V AC/DC with overvoltage category II and fulfilled enclosure protection
class between the supply, signal and relay circuits.
Sensor inputs (active) are energy limited circuits according to IEC/UL 61010 part 1.
15.2 Overview applications/functionality
The following charts provide an overview of the standard applications and functions of VEGAMET
800 series controllers. They give also information about whether the respective function can be
activated and adjusted via the integrated indicating and adjustment unit (OP) or via DTM/app.
5)
Applications (adjustable with DTM/app)
VEGAMET
Adjustment
841
842
861
862
OP
DTM/
App
Universal
•
•
•
•
•
•
5)
OP: Operating Panel (integrated display and adjustment unit)