![Vega VEGAMET 341 Operating Instructions Manual Download Page 52](http://html1.mh-extra.com/html/vega/vegamet-341/vegamet-341_operating-instructions-manual_3826802052.webp)
52
14 Supplement
VEGAMET 341 • 4 … 20 mA
63730-EN-210616
Ʋ
Wire cross-section massive wire,
strand
0.2 mm² (AWG 24) … 2.5 mm² (AWG 12)
Ʋ
Wire cross-section strand with end
sleeve
0.25 mm² … 1.5 mm²
Terminals current output
Ʋ
Type of terminal
Spring-loaded terminal
Ʋ
Wire cross-section massive wire,
strand
0.2 mm² (AWG 24) … 1.5 mm² (AWG 16)
Ʋ
Wire cross-section strand with end
sleeve
0.25 mm² … 1.5 mm²
Indicators
Measured value indication
Ʋ
Graphic-capable LC display, with
lighting
70 x 45 mm, digital and quasianalogue display
Ʋ
Indication range
-9999999 … 9999999
LED displays
Ʋ
Status, operating voltage
LED green
Ʋ
Status, fault signal
LED red
Ʋ
Status, operating relay
LED yellow
Status display via background lighting
Colour signalling according to NAMUR NE 107 (red/
orange/yellow/blue) or freely configurable
Adjustment
Adjustment elements
Turn/Push button
PC/Notebook
PACTware/DTM
Smartphone/Tablet
VEGA Tools app
Ambient conditions
Ambient temperature
Ʋ
Instrument in general
-20 … +60 °C (-4 … +140 °F)
Ʋ
Display (readability)
-20 … +60 °C (-4 … +140 °F)
Storage and transport temperature
-40 … +80 °C (-40 … +176 °F)
Relative humidity
< 96 %
Mechanical environmental conditions
Vibrations (oscillations)
Class 4M4 acc. to IEC 60721-3-4 (1 g, 4 … 200 Hz)
Impacts (mechanical shock)
Class 6M4 acc. to IEC 60721-3-6 (10 g/11 ms,
30 g/6 ms, 50 g/2.3 ms)
Electrical protective measures
Protection rating
Ʋ
Front
IP40 (IEC 60529)
Ʋ
Instrument
IP20 (IEC 60529)