43
10 Applications and functions
VEGAMET 341 • 4 … 20 mA
63730-EN-210616
Define adjustment values
Enter the adjustment values of the measuring point for 0 % and for
100 %.
Scaling
Enter the measured value and unit (e.g. flow rate in m³/h) and the cor
-
responding scaling values for 100 % and 0 % (e.g. 100 m³/h, 0 m³/h).
Activate/define totalizer
The flow value can also be summed up and displayed as flow rate.
Two independent totalizers are per measuring point available for this
purpose. Define the measuring unit and the display format. In addi
-
tion, a value for leak flow volume suppression can be defined.
Resetting the totalizer can be initiated as follows:
•
via the display and adjustment module
•
via the DTM/VEGA Tools app
•
via a digital input (e.g. via button)
•
time controlled (daily at any time)
Configure measured value indication
In the last step you can configure which and how many measured
values are to be shown on the display. In addition, you can define
the base of the display value, the display format and the optional bar
graph.