33
10 Diagnostics and servicing
VEGABAR 29 • Two-wire 4 … 20 mA
57087-EN-210301
Code
Text message
Cause
Rectification
F261
Error in the instrument set-
tings
Checksum error in the configuration
values
Carry out a reset
Code
Text message
Cause
Rectification
C700
Simulation active
A simulation is active
Finish simulation
Wait for the automatic end after
60 mins.
Code
Text message
Cause
Rectification
S600
Impermissible electronics
temperature
Temperature of the electronics in the
non-specified range
Check ambient temperature
Insulate electronics
S604
Switching output overloaded
Overload or short circuit at output 1 or 2 Electrical connection, check load re-
sistance
Code
Text message
Cause
Rectification
M504
Error at a device interface
Interference of the internal communica-
tion to Bluetooth
Restart
Send instrument for repair
M510
No communication with the
main controller
Fault in internal communication with the
display
Restart
Send instrument for repair
10.5 Software update
The device software is updated via Bluetooth.
The following components are required:
•
Instrument
•
Voltage supply
•
PC/notebook with PACTware/DTM and Bluetooth USB adapter
•
Current instrument software as file
You can find the current instrument software as well as detailed infor
-
mation on the procedure in the download area of our homepage.
Caution:
Instruments with approvals can be bound to certain software versions.
Therefore make sure that the approval is still effective after a software
update is carried out.
Function check
Out of specification
Maintenance