28
9 Menu overview
VEGABAR 29 • Two-wire 4 … 20 mA
57087-EN-210301
9 Menu overview
9.1 VEGA Tools app and DTM (Bluetooth)
Menu item
Device information
Actual measured values
Device status
Start image
Device name, software ver-
sion, serial number
Pressure, output current, measur-
ing cell temperature, electronics
temperature, sensor TAG
OK, error indication
Menu item
Parameter (code acc. to VD-
MA 24574-1)
Editing section
Basic setting
Measurement loop name
Measurement loop name
19 alphanumeric characters/
special characters
Sensor
Current output
Zero 4 mA (ZEO)
Measuring range begin …
measuring range end
Measuring
range begin
Span 20 mA (SPN)
Measuring
range end
Reaction in case of fault (FER)
≤ 3.6 mA, ≥ 21 mA
≤ 3.6 mA
360° status display (free
signalling)
Brightness (LED)
0 %, 10 %, 20 … 100 %
100 %
Signalling
Acc. to NAMUR NE 107, free
signalling
Switching out-
put
Fault
Red, yellow …, individual colour
selection, no signalling
Yellow
Flashing
Yes, no
No
Operating states
Operating states 1, 2, 3, 4, 5
1
Upper limit
Measuring range begin …
measuring range end
Colour selection
Red, yellow …, individual colour
selection, no signalling
Yellow
Flashing
Yes, no
No
Menu item
Parameter (code acc. to VD-
MA 24574-1)
Editing section
Basic setting
Damping
Damping (DAM)
0 … 9.999 s
0 s
Activate thermo-shock sup-
pression
Yes, no
No
Offset correction
Offset correction (OFS)
Execute, automatic correction
0,000 bar
Adjustment with medium
Apply min. pressure on the sen-
sor
Accept 4 mA (LRV)
-
Apply max. pressure on the
sensor
Accept 20 mA (URV)
Start image (app)
Main menu
Extended functions