Console Installation
Mounting the Console
9
Figure 4. Recommended Mounting of Console - Alternate Installations
Legend for numbered boxes
1
To an optional overfill alarm
2
Communication cable.
3
A dedicated circuit breaker rated for 15 amperes, 120 Vac or 240 Vac. NOTE, circuit breaker must be marked as the power
disconnect for the console. Run three 14 AWG standard color coded wires; live, neutral, and earth, to the console. Run one
12 AWG wire, color coded green, from the earth bus bar at the distribution panel direct to the console location. Leave enough
free cable for connection to the console.
4
Conduit for probe field cables.
consoles\tls2\mntUS.eps
2
1
3
4