TCP/IP Interface Module Installation
TLS Console Setup of the TCP/IP Interface Module
8
5. When you are finished, make sure any unused slots in the Comm cage have a blank end plate installed. Leave
the console door open.
TLS Console Setup of the TCP/IP Interface Module
1. Close and secure the console front door. Restore power to the console.
2. You will need to know what version software is installed in the console to properly setup the
TCP/IP
module.
Press the front panel MODE key to access Diag Mode. Press FUNCTION key to access System Diagnostic:
Press the STEP key to view the software revision level:
Where YY equals the console’s installed software. For example, if the version is 123.02, the software version
is 23.
Legend for numbered
boxes in Figure
1. J2/J3 jumper positions if
installing TCP/IP module
in slots 1-3 (default
positions)
2. Move jumpers J2/J3 onto 2
top pins if installing TCP/
IP module in slot 4
3. J1 connector
4. Interconnecting cable from
the kit (P/N 330020-425)
5. J6 on ECPU board
Figure 6. Installing TCP/IP Module in TLS-350/ProMax Comm Bay Slot 4
SYSTEM DIAGNOSTIC
PRESS <STEP> TO CONTINUE
SOFTWARE REVISION LEVEL
VERSION XYY.XX