background image

     

Page

 

22

Mag Sensor Alarms

MMM DD, YYYY HH:MM XM
s1: FUEL ALARM

(Flashing Red light)

MMM DD, YYYY HH:MM XM
s1: WATER ALARM

(Flashing Red light)

ALARM

TEST

ALARM

TEST

CAUSE:

Monitored parameter exceeded preset 
threshold.

ACTION:

Call for service following the procedures 
established for your site.

CAUSE:

Monitored parameter exceeded preset 
threshold.

ACTION:

Call for service following the procedures 
established for your site.

MMM DD, YYYY HH:MM XM
s1: COMMUNICATION ALARM

(Flashing Red light)

ALARM

TEST

CAUSE:

Hardware failure - sensor or inter-
connecting wiring to console.

ACTION:

Call for service following the proce-
dures established for your site.

Pump Relay Monitor Alarm

MMM DD, YYYY HH:MM XM
r1: PUMP RELAY ALARM

(Flashing Red light)

ALARM

TEST

CAUSE:

Pump continues to run after it was 
instructed to stop, or pump continu-
ously running longer than preset time.

ACTION:

Call for service following the proce-
dures established for your site.

Summary of Contents for TLS-3 Series

Page 1: ...TLS 3XX Series Consoles Operator s Quick Help Manual No 576013 939 Rev F...

Page 2: ...or use of this publication Veeder Root reserves the right to change system options or features or the information contained in this publication This publication contains proprietary information which...

Page 3: ...d Alarms 12 In Tank Warning And Alarm Levels 13 In Tank Alarms 14 HRM Alarms International Only 18 Dual Float Discriminating Sensor Alarms 19 Groundwater Sensor Alarms 20 Liquid Sensor Alarms 21 Mag S...

Page 4: ...nance Tracker White Maintenance Report keys available Version 27 and later Operating Keys Alphanumeric Keys MMM DD YYYY HH MM XM ALL FUNCTIONS NORMAL MODE BACKUP FUNCT TION PRINT CHANGE STEP PAPER FEE...

Page 5: ...em mode Operating Mode Setup Mode Diag nostic Mode Press to move to the next proce dure within each function The zero key has a space q a hyphen and the comma Press white key to print out the Mainte n...

Page 6: ...ously monitoring any sales from the tank being delivered to Within 60 minutes after printing the Inventory Increase Report the TLS 350R generates an Adjusted Delivery Report The TLS 350R adjusts the g...

Page 7: ...s FAIL on the report HOURLY RECONCILIATION MONITORING optional if enabled in setup DD MM YY RECONCILIATION REPORT T 1 4 FOUR STAR T 2 UL UNLEADED T 3 SU SUPER UNLEADED T 4 DV DIESEL TNK POS NEG AVE ST...

Page 8: ...onciliation process are available as Reconciliation Reports These reports are available for each worked shift for each day or for any other specified period TO PRINT A RECONCILIATION REPORT Press Mode...

Page 9: ...ing options such as printing weekly or periodic reports TO PRINT DELIVERY VARIANCE REPORTS Press Mode until the display reads Press Function until the display reads Press Print to printout the daily D...

Page 10: ...YSIS PRESS STEP TO CONTINUE Variance Reports Continued Maintenance Report Press the White Maintenance Report key on the front panel and the display reads Press Print to print the default number of rec...

Page 11: ...L FUNCTIONS NORMAL IN TANK TEST RESULTS PRESS STEP TO CONTINUE Press Print for a complete inventory report for all tanks To access the inventory information from each tank press Function until the dis...

Page 12: ...tank Press Print to print the report MMM DD YYYY HH MM XM ALL FUNCTIONS NORMAL LAST SHIFT INVENTORY PRESS STEP TO CONTINUE Press Function once and Step until you see the Deliv ery message the last de...

Page 13: ...il the display reads Press Tank until the desired product is visible in the display If necessary press Step until the date time of the delivery appears Press Print to print out a copy of that ticketed...

Page 14: ...conditions exist the system displays the message SENSOR NORMAL SMART SENSOR STATUS PRESS STEP TO CONTINUE s Location Status Indicator Mag Sump Sensor Leak Test Results In the operating mode press Fun...

Page 15: ...or warning exists the console will flash the mes sages alternately WARNINGS These indicate that an in tank alarm is imminent or that a system fault has occurred ALARMS Alarms indicate a potentially da...

Page 16: ...Volume Limit Full Volume Typical North American Tank Typical European Tank SAFE WORKING CAPACITY Maximum Product Alarm Level Overfill Alarm Level High Product Alarm Level Fuel Draw Off Level Delivery...

Page 17: ...lished for your site CAUSE Fuel level in the tank is below the Deliv ery Needed level ACTION Arrange a delivery CAUSE Fuel and water level floats on the probe are too close together due to a lack of f...

Page 18: ...ssible leak ACTION Call for service following the proce dures established for your site CAUSE Water at the bottom of the tank has exceeded the High Water Alarm level ACTION Close all pumps attached to...

Page 19: ...a possible leak fuel being dis pensed or other unauthorized loss ACTION Check that fuel has not been dispensed from the tank during the test period Call for service following the procedures establish...

Page 20: ...ully completed within the pre set time period ACTION Schedule a 0 2 gph 0 76 lph test CAUSE An annual in tank leak test has not been successfully completed within the preset time period ACTION Schedul...

Page 21: ...procedure for wetstock variances CAUSE The difference between the volume of fuel dispensed and the volume of fuel drawn from the tank has exceeded the Reconciliation Alarm Threshold ACTION Investigate...

Page 22: ...detected fuel vapor or liquid ACTION Investigate the cause of the alarm and take appropriate action CAUSE The sensor at the location shown has detected at least 8 inches 20 3 cm of non hydrocarbon li...

Page 23: ...gate the cause of the alarm and take appropriate action CAUSE The groundwater sensor at the location shown is inoperative ACTION Call for service following the procedures established for your site CAU...

Page 24: ...opriate action CAUSE The sump sensor has been disconnect ed or is faulty ACTION Call for service following the procedures established for your site CAUSE The Interstitial Monitor for the tank has dete...

Page 25: ...ce following the procedures established for your site MMM DD YYYY HH MM XM s1 COMMUNICATION ALARM Flashing Red light ALARM TEST CAUSE Hardware failure sensor or inter connecting wiring to console ACTI...

Page 26: ...ailure Dis pensing halts if programmed to do so while the alarm is active ACTION Consult W PLLD Alarm Quick Help Guide and Pressure Line Leak Diag Diagnostic Mode CAUSE 0 2 gph 0 76 lph test failure D...

Page 27: ...m alarm will be posted in the future ACTION Find and repair vacuum leak then perform a Vac Sensor Manual Test Diag Mode CAUSE There is no vacuum in the interstitial space ACTION Find and repair vacuum...

Page 28: ...e vapor sensor has been disconnected or is inoperative ACTION Call for service following the procedures established for your site MMM DD YYYY HH MM XM V1 WATER ALARM MMM DD YYYY HH MM XM V1 SHORT ALAR...

Page 29: ...aper see Changing the Printer Paper CAUSE Either the printer release lever is in the down position or the printer is inopera tive ACTION Check that the paper release lever is in the up position and if...

Page 30: ...continue Enter the Test Duration in hours press Enter and Step The display reads Press Enter to start the test For individual tanks press Tank to go to the next tank START IN TANK LEAK TEST PRESS STEP...

Page 31: ...to halt the test The system confirms the ending of the test by displaying STOP IN TANK LEAK TEST PRESS STEP TO CONTINUE STOP LEAK TEST TANK X PRESS ENTER LEAK TEST NOT ACTIVE PRESS FUNCTION TO CONT TO...

Page 32: ...he system s mem ory If fuel is dispensed from or delivered to the tank during the four hour period the test is stopped and no test results are stored A Quiet Period Leak Detection test requires a quie...

Page 33: ...st options you will not see these selections START LINE PRESSURE TEST PRESS STEP TO CONTINUE SELECT LINE ALL LINES SELECT TEST TYPE 3 0 GPH To select a 3 0 gph test press Step or press Change to selec...

Page 34: ...shown or press Change until you see the line you want to select then press Enter The system stops the test and displays the status message STOP LINE PRESSURE TEST PRESS STEP TO CONTINUE SELECT LINE A...

Page 35: ...ot have 0 2 or 0 1 gph test options you will not see these selections START LINE PRESSURE TEST PRESS STEP TO CONTINUE SELECT LINE ALL LINES SELECT TEST TYPE 3 0 GPH To select a 3 0 gph test press Step...

Page 36: ...ine shown or press Change until you see the line you want to select then press Enter The system stops the test and displays the status message STOP WPLLD LINE TEST PRESS STEP TO CONTINUE SELECT LINE A...

Page 37: ...press Enter The display reads Press Step four times to display the date If the date is correct press Step if not press Change and enter the correct date Note that the month must be entered first Pres...

Page 38: ...twice to return to the Operating mode To change the time press Change and enter the correct time Select either AM or PM by using the arrow keys Press Enter to confirm the time The display reads If the...

Page 39: ...ed guide 4 If the take up spool 2 has been used pull out the spool with the printed reports and tear off the paper close to the printer feed roller 5 2 8 7 9 Pull out the take up spool 2 and separate...

Page 40: ...9 between the two halves and press them firmly together until you hear a click Push the Take up Spool 2 into the upper slots Rotate the spool counterclockwise until you remove all slack in the paper I...

Page 41: ...For technical support sales or other assistance please visit www veeder com...

Reviews: