Liquid Sensor Alarms
MMM DD, YYYY HH:MM XM
L1: FUEL ALARM
MMM DD, YYYY HH:MM XM
L1: SENSOR OUT ALARM
(Flashing Red light)
(Flashing Red light)
ALARM
TEST
ALARM
TEST
MMM DD, YYYY HH:MM XM
L1: INTERSTITIAL ALARM
(Flashing Red light)
ALARM
TEST
DD-MM-YY HH:MM:SS
L1: INTERCEPTOR ALARM
(Flashing Red light)
ALARM
TEST
CAUSE:
The sensor has detected liquid in the
sump being monitored.
ACTION:
Investigate the cause of the alarm and
take appropriate action.
CAUSE:
The sump sensor has been disconnect-
ed or is faulty.
ACTION:
Call for service following the procedures
established for your site.
CAUSE:
The Interstitial Monitor for the tank has
detected a change in the interstitial fluid
level; a fuel leak may have occurred.
ACTION:
Call for service following the proce-
dures established for your site.
CAUSE:
A sensor installed in a drainage intercep-
tor trap has detected fuel.
ACTION:
Call for service following the procedures
established for your site.
Note that interceptor sensors will also
warn of high and low liquid levels in the
interceptor.