Page
20
Groundwater Sensor Alarms
MMM DD, YYYY HH:MM XM
G1: FUEL ALARM
MMM DD, YYYY HH:MM XM
G1: SENSOR OUT ALARM
(Flashing Red light)
(Flashing Yellow light)
ALARM
TEST
ALARM
TEST
MMM DD, YYYY HH:MM XM
G1: WATER ALARM
MMM DD, YYYY HH:MM XM
G1: SHORT ALARM
(Flashing Yellow light)
(Flashing Yellow light)
ALARM
TEST
ALARM
TEST
CAUSE:
The groundwater sensor has detected
fuel.
ACTION:
Investigate the cause of the alarm and
take appropriate action.
CAUSE:
The groundwater sensor at the location
shown is inoperative.
ACTION:
Contact your VR Service Contractor for
advice
CAUSE:
The water level in the monitoring well
shown is below the groundwater
sensor (this may occur during
periods of severe drought).
ACTION:
If the condition persists contact your
VR Service Contractor for advice.
CAUSE:
The groundwater sensor at the
location shown is inoperative.
ACTION:
Contact your VR Service Contractor
for advice.