Page
13
In-Tank Alarms
MMM DD, YYYY HH:MM XM
T1: HIGH WATER WARNING
(Flashing Yellow light)
(Flashing Yellow light)
MMM DD, YYYY HH:MM XM
T1: INVALID FUEL LEVEL
ALARM
TEST
ALARM
TEST
CAUSE:
Water collecting in the tank has
exceeded the Water Warning level.
ACTION:
Close all pumps attached to this tank.
Contact your VR Service Contractor
for advice.
CAUSE:
Fuel level in the tank is below the
Delivery Needed level.
ACTION:
Arrange a delivery.
CAUSE:
Fuel and water level floats on the
probe are too close together due to a
lack of fuel in the tank.
ACTION:
Arrange a delivery.
(Flashing Yellow light)
MMM DD, YYYY HH:MM XM
T1: TANK TEST ACTIVE
ALARM
TEST
ALARM
TEST
MMM DD, YYYY HH:MM XM
T1: DELIVERY NEEDED
(Flashing Yellow light)
CAUSE:
If enabled, the system will display this
message when a tank test is in
progress.
ACTION:
Do not deliver to or dispense from the
tank being tested.