  Introduction

Overview

A Diesel Exhaust Fluid (DEF) Recirculating Temperature Sensor monitors the temperature in the DEF fluid 
between the DEF tank and the DEF dispensers to prevent DEF fluid from freezing in the lines or degrading at high 
temperatures (see Figure 1). When the sensed temperature drops or rises to a preset temperature, the ATG can 
turn on the DEF pump to recirculate the DEF fluid throughout the piping until the product temperature reaches a 
preset stop temperature. The ATG can also control a customer supplied Heat Trace System independently or 
concurrently with the DEF pump.

Figure 1.   DEF Fluid Temperature Monitoring Components

DEF Dispenser

DEF Dispenser

Heat Trace manufacturer required 
GFI EPD circuit breaker per NEC 
Article 427-22

To optional 

Heat Trac

DEF Temperature Sensor

(Up to 2 depending on 

application requirements)

Mag

Probe

DEF Tank

MP

H

Controller

Hook

Pump Power

H

TS

Pump

L

L
N

N

G

T 2: DELIVERY NEEDED

12/20/2012 06:01 PM

Tank Overview

TANK 1: reg

Fuel Volume

3655

Fuel Height

38.6

Ullage 100%

6345

Temperature

61.9

Water Height

3.0

1 Warning(s)

0 Alarms(s)

Print (0)

Home

Favorites

Menu

Actions

Overview

TANK 2: diesel

Fuel Volume

1600

Fuel Height

20.6

Ullage 100%

8345

Temperature

60.8

Water Height

0.0

!

From

Distribution

Panel

Intrinsically safe

Intrinsically safe

Summary of Contents for DEF

Page 1: ...Manual No 577014 344 Revision C Installation Manual DEF Recirculation Control...

Page 2: ...f any damages and or shortages within 30 days of receipt of the shipment as stated in our Terms and Conditions VEEDER ROOT S PREFERRED CARRIER 1 Fax Bill of Lading to V R Customer Service at 800 234 5...

Page 3: ...ensor Field Wiring 9 Sealing Field Connections 9 Wiring Run Through Rigid Conduit 9 Direct Burial Cable 10 Console Wiring Precautions 10 Connecting Sensor Wiring To The Console 11 Figures Figure 1 DEF...

Page 4: ...dependently or concurrently with the DEF pump Figure 1 DEF Fluid Temperature Monitoring Components DEF Dispenser DEF Dispenser Heat Trace manufacturer required GFI EPD circuit breaker per NEC Article...

Page 5: ...install intrinsically safe apparatus use the specific control drawing that appears on the nameplate of the applicable associated apparatus ATG Console The control drawings contain information related...

Page 6: ...Operator s Manual CLASS I Division 1 Group D CLASS 1 Zone 0 Hazardous Location Intrinsically Safe Apparatus DEF Temperature Sensor Intrinsically Safe Wiring White Brown Black Black I S Rigid Conduit...

Page 7: ...o alert you to important safety hazards and precautions GENERAL Ensure that all local council and regulations are complied with Also ensure that all recognized safety codes are followed EXPLOSIVE Fuel...

Page 8: ...energy limited system This system makes the sensors suitable for use in hazardous locations Sensor wiring is intrinsically safe only when connected to the TLS console All sensor wiring must be contai...

Page 9: ...service this equipment in accordance with these codes regulations and standards may lead to legal citations with penalties or affect the safe use and operation of the equipment ISO STANDARD FOR DEF Th...

Page 10: ...must be observed Keep fluid away from the motor cable Follow internal instructions Wear protective clothing face and breathing protection protective gloves etc De ploy safety barricades around work a...

Page 11: ...d install it into the bushing 4 Loosen the nut on the tube fitting and insert the temperature sensor into the tube fitting enough but not more than 6 to ensure the 1 4 diameter section of the sensor i...

Page 12: ...ugh the seal off box the conduit attaching the junction box to the seal off box and into the junction box 2 Using wire nuts connect the two wires from the sensor to the two wires coming from the conso...

Page 13: ...nec tors without reprogramming that device 879 38 eps To console Tie wrap Wire nuts From probe sensor or transducer A C B Make sure that the ends of cable sheathing are sub merged in sealant nt t t nt...

Page 14: ...sensor is NOT grounded 3 Write in the device name for each wire connection on the connector block in the module s wiring label attached to the inside of the door 4 Make sure that you loop the wire nea...

Page 15: ...m Relay Contact Ratings 120 240 Vac 5A 30 Vdc 5A Fuse ratings 5A 250 Vac Type T Slo Blo TLS 450PLUS TLS XB TLS4 Control Of DEF Piping Heat Trace Circuitry If Required HV Relay Outputs Control Of DEF P...

Page 16: ...For technical support sales or other assistance please visit www veeder com...

Reviews: