Low Speed NPN Input: 

 Configures the unit to accept a sinking or dry contact input and sets a filtering

speed of 30 Hz

High Speed NPN Input:  

Configures the unit to accept a sinking or dry contact input of up to 7.5 kHz

Low Speed PNP Input:  

Configures the unit to accept a sourcing input and sets a filtering speed of 30  Hz

L0 NPN

L0 PNP

PNP

1 NPN

H

H1

High Speed PNP Input:

  Configures the unit to accept a sourcing input of up to 7.5 kHz

loc

unloc

Hold for 2 seconds

Front Panel Reset Locked:

  Pressing the front panel reset key during operation will not reset the

accumualted count/time value

Front Panel Reset Unlocked:

  Pressing the front panel reset key during operation will cause the

accumualted count/time value to be reset.

Hold for 2 seconds to return to Operating Mode

Note:  This choice will not appear for Time Totalizer models

Process Value Display

Displays the count, time or rate
value based upon the model

Front Panel Reset

On Time or Count models, used to
reset the Process Value Display.
May be disabled through the
keylock input.  Also used to perform
Programming mode functions

Your C342 has been configured at the factory to perform  one of the following functions:

To access Input Configuration Parameters:

• Enter the Program Mode by holding the Front Panel Reset (FPR) key during power-up
• Scroll throuugh the 4 input configuration choices by brief press and release of the FPR key
• When the desired choice appears, hold down the the FRP key for seconds to select it
• Scroll between the two Front Panel Enable choices by brief press and release of the FPR key.

Hold the FPR key for 2 sconds to select the desired choice and return to Operating Mode

Note: The NPN/PNP selection applies to the Signal, Reset,  and Hold inputs

PROGRAMMING

During Power-up

C342-0562 Totalizer:

  The instrument will accumulate and display

the pulses received on the count input terminals (2 & 4).  Count
capacity is 8 digits: 

123456 

The total can be reset via the remote

reset terminals (2 & 5) or the front panel.

C342 -8562 Position Indicator

:  The instrument will count in a bi-

directional mode based on the quadrature input from an encoder
(terminals 2,5 & 7).  Display range is -99999 to 99999.

C342-1562 Time Totalizer #1:

 The instrument will accumulate time

when the input signal (terminals 2 & 4) is active. The time will be
displayed in the format:  

99:59:59

  Hours:Minutes:Seconds and can be

reset via the remote reset terminals (2 & 5) or the front panel.

C342-2562 Time Totalizer #2:

 The instrument will accumulate time

when the input signal (terminals 2 & 4) are active.  The time will be
displayed in hours with 1/100 resolution 

 9999.99 

and can be

reset via the remote input terminals (2 & 5) or the front panel.

C342-3562 Tachometer:

  Pulses received on the input terminals (2

& 3) are sampled for a 6 second period then displayed as a rate
value in units per minute:  

999990

    A Display Hold function

(terminals 2 & 7) will freeze the current reading.

C342-4562 Message Display

:  The instrument will display

alpahumeric messages based on a digital input from a PLC  Please
refer to separate insruction sheet which provides specific
information on how to interface to a PLC.

Summary of Contents for C342 Series

Page 1: ...tory programmable features Setpoint Scale Value Decimal Position Text Message IEC IP65 rated front panel for use in washdown environments Index Overview Installation page 2 Terminal Connections page 2 Setup Front Panel Operation page 3 Programming page 3 General Specifications page 4 Ordering Information page 4 Warranty page 4 Models Covered in this Manual C342 0464 Totalizer Accumulates and displ...

Page 2: ...nals are accumu lated for count and tachometer versions For timer versions the timerrunswhencontactisclosed See Programming to select low speed NPN mode Channel B Wiring Insert wire into the appropriate openings as pictured in the drawing below Turn the screws located on the rear of the terminal block to tighten the clamp and secure the wire Solid State Output When the factory programmed preset va...

Page 3: ... down the the FRP key for seconds to select it Scroll between the two Front Panel Enable choices by brief press and release of the FPR key Hold the FPR key for 2 sconds to select the desired choice and return to Operating Mode Note The NPN PNP selection applies to the Signal Reset and Hold inputs PROGRAMMING During Power up C342 0562 Totalizer The instrument will accumulate and display the pulses ...

Page 4: ...y Programmable Settings Setpoint Prescale Value Decimal Position Text Message Specifcy the setting and value when placing an order Ex Setpoint 4567 Standard products manufactured by the Company are warranted to be free from defects in workmanship and material for a period of one year from the date of shipment and products which are defective in workmanship or material will be repaired or replaced ...

Reviews: