Mounting location

 

 

Install the controller on an easy accessible interior wall, approx. 1.5 m above the floor in an area of average 

temperature. 

 

Avoid direct sunlight or other heat sources, e.g. the area above radiators and heat emitting equipment.  

 

Avoid locations behind doors, outside walls and below or above air discharge grills and diffusers.  

 

Location of mounting is less critical if external temperature sensors are used. 

Installation 

1.

 

Connect the wires to be connected to the terminals of the power case according to wiring diagram 

2.

 

Install the mounting plate to the flush mounting box. Make sure that the nipple with the front holding screw is 

facing to the ground. Make sure the mounting screw heads do not stand out more than 5 mm (0.2”) off the 

surface of the mounting plate.  

3.

 

Ensure that the jumpers are set correctly.  

4.

 

Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate.  

5.

 

Carefully lower the front part until the interconnector reaches the mounting-plate. Continue pressing in a gentle 

way until the front part is fully connected. While inserting the connectors, a slight resistance can be felt. This is 

normal. Do not use excessive force!  

6.

 

With a Philips-type screw driver of size #2, carefully tighten the front holding screw to secure the front part to 
the mounting plate. This screw is located on the front lower side of the unit. There is no need to tighten the 

screw too much. 

Wiring Diagram 

 

Description:  

Power supply:  

0V Neutral 

Power supply:  

-24: 24VAC/DC, -120: 120VAC, -230: 230VAC 

Y1 

Binary output:  

Fan speed low 

Y2 

Binary output:  

Fan speed medium 

Y3 

Binary output:  

Fan speed high 

Y4 

Binary output:  

Heating Valve or OPEN if in 3-point floating mode 

Y5 

Binary output:  

Cooling Valve or CLOSE if in 3-point floating mode 

 

 Cool / 

Close 

X

T INT 

0V 

Power 

 

TLC3-FCR-2T-U 

Y1 

Fan 

Low 

Y2 

Fan 

Med 

Y3 

Fan 

High 

Y4 

Heat / 

Open 

Y5 

Summary of Contents for TLC3-FCR-2T-U

Page 1: ...ves or 3 point on off or floating control of one 3 point valve General Description The TLC3 FCR 2T is a stand alone electronic fan coil controller with one control loop The TLC3 FCR 2 features 1 NTC t...

Page 2: ...idity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 C 70 C 13 F 158 F 95 R H non condensing class 2M2 Standards conformity EMC Directive Low Voltage Directive 2004...

Page 3: ...unting plate 3 Ensure that the jumpers are set correctly 4 Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate 5 Carefully lower the front...

Page 4: ...on to operate accordingly Frost Protection The controller will enter frost protection mode if the room temperature drops below 5 C 41 F All heating outputs will be fully opened Frost protection mode w...

Page 5: ...ptions d1 7 d1 6 d1 5 d6 7 day1 day2 day3 day4 day5 day6 day7 Day 1 stands for Monday day 2 for Tuesday and so forth Press OPTION to save day selection Pro1 d1 7 Step 3 Selected action of first switch...

Page 6: ...the temperature loop may be changed Set point range is 15 to 30 C Changing of fan speeds Repeatedly pressing the fan speed button steps through low medium high and automatic fan speeds Automatic fan s...

Page 7: ...UP 01 Enable change of set points ON OFF ON Enabled UP 02 Enable manual control of fan speeds ON OFF ON Enabled UP 03 Enable change of heating cooling mode ON OFF W00 ON Enabled W01 OFF Disabled UP 0...

Page 8: ...FC 05 Switching Span Heating Setting this value to 0 disables the auto fan speed function in heating mode 0 10 0 C 20 0 F 1 5 C 3 F FC 06 Switching Span Cooling Setting this value to 0 disables the a...

Page 9: ...nary output DO4 open DO5 close 2 3 point floating output DO4 open DO5 close 0 2 0 Binary PWM FC 17 Running Time in 3 point mode 0 255 s 90 s FC 18 PWM cycle timeheating 0 disables PWM mode 0 100 min 0...

Page 10: ...TLC3 FCR 2T U Engineering Manual Doc 70 00 0203 V3 0 Date 20121119 Vector Controls GmbH Switzerlandmailto info vectorcontrols com Page 10 Subject to alteration Notes...

Reviews: