TLC3-FCR-2T-U Engineering Manual

 

 

Doc: 70-00-0203, V3.0 Date: 20121119 

© Vector Controls GmbH, Switzerland

mailto:[email protected]

 

Page 2 

Subject to alteration 

Technical Specification 

Power Supply 

Operating Voltage 

-24 

-120 

-230 

 

AC voltage: 50/60Hz 

22-26VADC 

100-130 VAC 

210

–250 VAC 

 

Power Consumption 

Max 1W, 1.5 VA 

 

Electrical Connection 

Terminal Connectors 

 

Deluxe only:Power backup for real time clock 

Min 48h if charged for 24h 

Signal Inputs 

Temperature Inputs 

Range 
Accuracy 

RT Internal 
0…50 °C (32…122 °F) 
0.5°C (1°F) 

Signal Outputs 

Digital Switching Outputs 

Switching Type 
AC Switching power 

DO1 to DO3 
Relays 
250V AC 2A max. each output 

 

Digital Switching Outputs 

DO4…DO5 

 

 

Switching Type 
AC Switching power 

-24: Relays 
       2A max. 

-120-230:  

TRIAC 

 

0.3A max 

 

Insulation strength 

between contacts and system electronics: 
between neighboring contacts 

 
3750V AC to EN 60 730-1 
1250V AC to EN 60 730-1 

Environment 

Operation 

Climatic Conditions 
Temperature 
Humidity 

To IEC 721-3-3 
class 3 K5 
0°C 

…50°C (32°F…122°F) 

<95% R.H. non-condensing 

 

Transport & Storage 

Climatic Conditions 
Temperature 
Humidity 
Mechanical Conditions 

To IEC 721-3-2 and IEC 721-3-1 
class 3 K3 and class 1 K3 
-25

°C…70°C (-13°F…158°F) 

<95% R.H. non-condensing 
class 2M2 

Standards 

conformity 
EMC Directive 
Low Voltage Directive 

2004/108/EC 
2006/95/EC 

 

Product standards 

Automatic electrical controls for household and similar use 
Special requirement on temperature dependent controls 

 
EN 60 730 

–1 

EN 60 730 

– 2 - 9 

 

Electromagnetic compatibility for  
domestic sector 

Emissions: EN 60 730-1 
Immunity: EN 60 730-1 

 

Degree of Protection 

IP30 to EN 60 529 

 

Pollution Class 

II (EN 60 730-1) 

 

Safety Class:  

for -24 types 
for -120 and -230 types 

III (IEC 60 536)  
II (IEC 60 536) 

 

Overvoltage Category:  

for -24 types 
for -120 and -230 types 

I (EN 60 730-1) 
III (EN 60 730-1) 

General 

Dimensions (H x W x D) 

Front part:  
Power case: 

16 x 73 x 113mm (0,7 x 2.9 x 4.5 in.)  
60 x 50 x 32mm (2.4 x 2.0 x 1.3 in.) 

 

Material:  

Cover, back part 
Mounting Plate 

Fire proof ABS plastic 
Galvanized Steel 

 

Weight (including package)  for -24 types 

for -120 and -230 types 

standard: 255g (9.0oz), deluxe: 265g (9.3oz) 
standard: 295g (10.5oz), deluxe: 305g (10.8oz) 

Dimensions 

 

 

Space required in flush mounting box: 

(H x W x D)  

60 x 50 x 32mm (2.4 x 2.0 x 1.3 in.) 

 

Distance for mounting screws: 
Horizontal 55 to 60mm (2.2 to 2.4 in.) 

Vertical: 55 to 93mm (2.2 to 3.7 in.) 
 

32 (1.3) 

16 (0.7) 

1

1

3

 (

4

.5

73 (2.9) 

Summary of Contents for TLC3-FCR-2T-U

Page 1: ...ves or 3 point on off or floating control of one 3 point valve General Description The TLC3 FCR 2T is a stand alone electronic fan coil controller with one control loop The TLC3 FCR 2 features 1 NTC t...

Page 2: ...idity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 C 70 C 13 F 158 F 95 R H non condensing class 2M2 Standards conformity EMC Directive Low Voltage Directive 2004...

Page 3: ...unting plate 3 Ensure that the jumpers are set correctly 4 Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate 5 Carefully lower the front...

Page 4: ...on to operate accordingly Frost Protection The controller will enter frost protection mode if the room temperature drops below 5 C 41 F All heating outputs will be fully opened Frost protection mode w...

Page 5: ...ptions d1 7 d1 6 d1 5 d6 7 day1 day2 day3 day4 day5 day6 day7 Day 1 stands for Monday day 2 for Tuesday and so forth Press OPTION to save day selection Pro1 d1 7 Step 3 Selected action of first switch...

Page 6: ...the temperature loop may be changed Set point range is 15 to 30 C Changing of fan speeds Repeatedly pressing the fan speed button steps through low medium high and automatic fan speeds Automatic fan s...

Page 7: ...UP 01 Enable change of set points ON OFF ON Enabled UP 02 Enable manual control of fan speeds ON OFF ON Enabled UP 03 Enable change of heating cooling mode ON OFF W00 ON Enabled W01 OFF Disabled UP 0...

Page 8: ...FC 05 Switching Span Heating Setting this value to 0 disables the auto fan speed function in heating mode 0 10 0 C 20 0 F 1 5 C 3 F FC 06 Switching Span Cooling Setting this value to 0 disables the a...

Page 9: ...nary output DO4 open DO5 close 2 3 point floating output DO4 open DO5 close 0 2 0 Binary PWM FC 17 Running Time in 3 point mode 0 255 s 90 s FC 18 PWM cycle timeheating 0 disables PWM mode 0 100 min 0...

Page 10: ...TLC3 FCR 2T U Engineering Manual Doc 70 00 0203 V3 0 Date 20121119 Vector Controls GmbH Switzerlandmailto info vectorcontrols com Page 10 Subject to alteration Notes...