TLC3-FCR-2 Engineering Manual
Doc: 70-00-0202, V3.0 Date: 20111027
© Vector Controls GmbH, Switzerland
Page 9
Subject to alteration
Control Configuration for PWM – 3-point floating mode
FC 14
P – band heating X
PH
0-10.0°C (20.0°F)
2.0°C (4.0°F)
FC 15
P – band cooling X
PC
0-10.0°C (20.0°F)
2.0°C (4.0°F)
Î
Proportional control (P-band)
The proportional control function calculates the output based on the difference between setpoint and measured
value. The proportional band (P-band) defines the difference between setpoint and measured value which will
result in a 100% output. Setting the proportional band to 0 disables proportional control.
Output configuration
FC 16
Output setting, Binary, PWM or 3-point:
0 = Binary or PWM (DO4 Heating, DO5 Cooling)
1 = 3-point binary output (DO4 open, DO5 close)
2 = 3-point floating output (DO4 open, DO5 close)
0…2 0
Binary / PWM
FC 17
Running Time in 3-point mode
0…255 s
90 s
FC 18
PWM cycle time heating, 0 disables PWM mode
0…100 min
0
FC 19
PWM cycle time cooling, 0 disables PWM mode
0…100 min
0
Î
3-point floating:
For floating point outputs the running time of the actuator used needs to be specified with FC17. Running time is
defined as the time required for the actuator to run from fully open to fully closed and vice versa. Actuators with a
fixed running time are recommended. Once fully open or fully closed the running time for the actuator is extended
for a full run-time cycle. This will allow the actuator position to be synchronized in case it has been moved during
off time or an actuator with variable running time was used.
Î
Pulse With Modulation (PWM)
In PWM mode the digital output will be switched on/off once per cycle. The on and off times are calculated
according to the control sequence.