TLC3-FCR-2 Engineering Manual

 

 

Doc: 70-00-0202, V3.0 Date: 20111027 

© Vector Controls GmbH, Switzerland 

Page 7 

Subject to alteration 

Setting of user parameters 

The TLC3-FCR-2 is an intelligent controller and can be adapted to fit perfectly into your fan coil application. The control 
operation is defined by parameters. The parameters are set during operation by using the standard operation terminal.  
The parameters are password protected. There are two levels of parameters: User operation parameters for access 
control settings and Expert parameters for control functions and unit setup. The passwords for user levels and expert 
levels are different. Only control experts should be given the control parameter password.  
The parameters can be changed as follows: 

1.

 

Press UP and DOWN button simultaneously for three seconds. The display will indicate the firmware version in 
the upper large digits and the revision in the lower small digits. Pressing any key will show: CODE. 

2.

 

Select a password using UP or DOWN buttons. Select 009 in order to get access to the user parameters, 241 
for controls parameters.  
Press OPTION after selecting the correct password.  

3.

 

Once logged in, the parameter is displayed immediately 

4.

 

Select the parameters with the UP/DOWN keys. Change a parameter by pressing the OPTION key. The MIN 
and MAX symbols show up and indicate that the parameter may be modified now. Use UP and DOWN key to 
adjust the value. 

5.

 

After you are done, press OPTION or POWER in order to return to the parameter selection level.  

6.

 

Press the POWER key again so as to leave the menu. The unit will return to normal operation if no key is 
pressed for more than 5 minutes. 

User Parameters 

Parameter Description 

Setting 

Range Factory 

Setting 

UP 00 

Enable change of operation modes  

ON, OFF 

ON (Enabled) 

UP 01 

Enable change of set points 

ON, OFF 

ON (Enabled) 

UP 02 

Enable manual control of fan speeds 

ON, OFF 

ON (Enabled) 

UP 03 

Enable change of heating/cooling mode 

ON, OFF 

W00: ON (Enabled) 
W01: OFF (Disabled) 

UP 04 

Enable access to Time programs 

ON, OFF 

ON (Enabled) 

UP 05 

State after power failure:  
0 = Switched OFF, 1 = Switched ON, 2 = state before power failure 

0, 1, 2 

UP 06 

Enable Economy (unoccupied) Mode.  
Shift the set point to a lower temperature in winter or higher 
temperature in summer in order to save energy. Economy mode 
may be activated through the POWER button, or with the external 
input (typically for key card switches in hotel rooms or motion 
detectors for meeting rooms.) 

ON, OFF 

ON (Economy ) 

UP 07 

Celsius or Fahrenheit, Select ON for Fahrenheit, OFF for Celsius 

ON, OFF 

OFF (Celsius) 

UP 08 

Calibration value of temperature sensor . This value is calibrated at 
manufacturing of the thermostat. If required it is possible to shift 
the temperature –10° to +10° in 0.1° K steps.  

-10…10 0 

UP 09 

Enable Frost Protection.  
Activates the output independent of operation mode when the 
control temperature drops below 5°C or 41°F. The controller 
returns to normal operation when the temperature increases above 
10°C or 50°F. 

ON, OFF 

W00 = ON  

(Frost Protection) 

W01 = OFF 

(No Frost Protection) 

UP 10 

Select contents of Large LCD display in standard mode: 
00  

= OFF 

01  

= Setpoint 

02  

= Temperature Sensor 

03  

= Output Fan Speed 

04  

= Clock 

0…4 02 

 

Temperature 

UP 11 

Select contents of small LCD display in standard mode 
(use table of UP 10) 

0…4 04 

Deluxe: 

 

show clock 

01 Standard:  

show setpoint 

UP 12 

Contents of vertical bar in standard mode 
OFF   = Fan Speed 
ON  

= Control output 

ON, OFF 

OFF (FAN) 

UP 13 

Deluxe only 

Clock display type:  
OFF 

= Show 24hour clock 

ON  

= Show 12hour clock (AM, PM) 

ON, OFF 

OFF (24h) 

UP 14 

Deluxe only 

Reset: applies when the unit is manually switched on, while in 
scheduled off mode. The unit will switch automatically back to the 
scheduled mode when the reset time expires.  

= Reset of override mode is not active.  

1…255 = delay in minutes to switch off device 

0…255 60 

(Min) 

 
 

Summary of Contents for TLC3-FCR-2

Page 1: ...ndividual room control for hotel rooms meeting rooms etc PWM or On Off Control of 2 spring return valves or 3 point on off or floating control of one 3 point valve General Description The TLC3 FCR 2 is a stand alone electronic fan coil controller with one control loop The TLC3 FCR 2 features 1 NTC temperature sensor input and five binary outputs Three outputs control a fan with low medium and high...

Page 2: ...chanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 C 70 C 13 F 158 F 95 R H non condensing class 2M2 Standards conformity EMC Directive Low Voltage Directive 2004 108 EC 2006 95 EC Product standards Automatic electrical controls for household and similar use Special requirement on temperature dependent controls EN 60 730 1 EN 60 730 2 9 Electromagnetic compatibility fo...

Page 3: ... Ensure that the jumpers are set correctly 4 Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate 5 Carefully lower the front part until the interconnector reaches the mounting plate Continue pressing in a gentle way until the front part is fully connected While inserting the connectors a slight resistance can be felt This is normal Do n...

Page 4: ...cordingly Frost Protection The controller will enter frost protection mode if the room temperature drops below 5 C 41 F All heating outputs will be fully opened Frost protection mode will be left once the temperature reaches 10 C 50 F Frost protection display will remain until a button is pressed Frost protection can be enabled disabled using user parameter UP 09 Error messages Following error con...

Page 5: ...1 5 d6 7 day1 day2 day3 day4 day5 day6 day7 Day 1 stands for Monday day 2 for Tuesday and so forth Press OPTION to save day selection Pro1 d1 7 Step 3 Selected action of first switching event One bar on the right side indicates the first switching event Press UP DOWN to select action for first switching event No switching event not active OFF switches unit off Reset UP17 active if switched to ON m...

Page 6: ...e changed Set point range is 15 to 30 C Changing of fan speeds Repeatedly pressing the fan speed button steps through low medium high and automatic fan speeds Automatic fan speed will not be activated in FAN ONLY mode Boost Pressing the boost button activates a 5 minute boost The output will be fully opened for the period of 5 minutes independent of demand This may be used to change stale air duri...

Page 7: ...nge of set points ON OFF ON Enabled UP 02 Enable manual control of fan speeds ON OFF ON Enabled UP 03 Enable change of heating cooling mode ON OFF W00 ON Enabled W01 OFF Disabled UP 04 Enable access to Time programs ON OFF ON Enabled UP 05 State after power failure 0 Switched OFF 1 Switched ON 2 state before power failure 0 1 2 2 UP 06 Enable Economy unoccupied Mode Shift the set point to a lower ...

Page 8: ...g Span Heating Setting this value to 0 disables the auto fan speed function in heating mode 0 10 0 C 20 0 F 1 5 C 3 F FC 06 Switching Span Cooling Setting this value to 0 disables the auto fan speed function in cooling mode 0 10 0 C 20 0 F 1 0 C 2 F FC 07 Switching Hysteresis is the difference between switching on and switching off A small hysteresis will increase the number of switching cycles an...

Page 9: ...pen DO5 close 2 3 point floating output DO4 open DO5 close 0 2 0 Binary PWM FC 17 Running Time in 3 point mode 0 255 s 90 s FC 18 PWM cycle time heating 0 disables PWM mode 0 100 min 0 FC 19 PWM cycle time cooling 0 disables PWM mode 0 100 min 0 Î 3 point floating For floating point outputs the running time of the actuator used needs to be specified with FC17 Running time is defined as the time re...

Page 10: ...TLC3 FCR 2 Engineering Manual Doc 70 00 0202 V3 0 Date 20111027 Vector Controls GmbH Switzerland Page 10 Subject to alteration Notes ...

Reviews: