background image

 

TCT-MZ 

Technical data 

 

Doc: 70-00-0588 V1.0, 20180928 

© Vector Controls GmbH, Switzerland 

Page 3 

Subject to alteration 

www.vectorcontrols.com 

Installation and Safety advice 

Caution!

 This device is intended to be used for comfort applications. Where a device failure endangers human life and/or 

property, it is the responsibility of the owner, designer and installer to add additional safety devices to prevent or detect a 
system failure caused by such a device failure. Vector Controls or its affiliates cannot be held liable for any damage 

caused by such a failure. Failure to follow specifications and local regulations may endanger life, cause equipment damage 

and void warranty.  

Connection diagram 

 

Description:  

G0 

Power supply:  

0V, -24VDC, internally connected to signal common 

Power supply:  

24VAC, +24VDC 

Signal common:  

Common 0 potential for analog inputs and analog outputs. 

X1

 

External passive input: 

open contact to signal common 

 

U1

 

Analog output supply air:  

0…10 V DC 

U2

 

Analog output return air:  

0…10 V DC 

 

Mounting location 

 

On an easy accessible interior wall, approx. 1.5 m (4.5’) above the floor in an area of average temperature. 

 

Avoid exposure to direct sunlight 

Installation 

Install on an easy accessible interior wall, approx. 1.5 m (4.5’) above the floor. Installation only on an on-wall or under-

wall box (frame and mounting plate is not included) 
Installation:  

1.

 

Connect the wires to be connected to the terminals of the power case according to wiring diagram 

2.

 

Install the mounting plate to the flush mounting box  

3.

 

Screw the power case to the metal plate. Connectors need to point upwards! 

4.

 

Place the frame on mounting plate and hold it with one hand 

5.

 

Take the display and place it in the middle of the frame, the thick side of the display frame need to point 

downwards 

6.

 

Verify that the 10 pin connector connects correctly 

7.

 

Carefully press the display on the power part until the clamps are clicking in (it may be required to move the 

frame slightly). 

0V (COM) 

24V AC/DC 

 

TCT-MZ2 

G0 

U1 

Supply 

OUT 

 

U2 

Return 

OUT 

 

  7 
  M  

Signal  

COM 

 

X1 

X

1

  

IN 

 

Summary of Contents for TCT-MZ

Page 1: ...plications Control of ventilation systems for comfort and industrial applications General description The TCT MZ is a microprocessor controlled precision positioner with real time clock and time sched...

Page 2: ...0 C 32 122 F 95 r H non condensing Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non...

Page 3: ...mmon U1 Analog output supply air 0 10 V DC U2 Analog output return air 0 10 V DC Mounting location On an easy accessible interior wall approx 1 5 m 4 5 above the floor in an area of average temperatur...

Page 4: ...are memorized and do not need to be reentered Depending on UP03 the unit will remain switched off switch on automatically or return to the operation mode it was in before the power failure Deluxe ver...

Page 5: ...schedules Press CLOCK key 2 sec Time schedule operation is enabled or disabled alternately Creating time schedules Step 1 Select a switching time Up to 8 Pr01 Pr08 Press CLOCK Key 2 sec SEL and curre...

Page 6: ...ct a password using UP or DOWN buttons Select 009 in order to get access to the user parameters Press OPTION after selecting the correct password 3 Once logged in the parameter is displayed immediatel...

Page 7: ...OFF 0V energy hold off 0 100 0 10V or 2 10V OFF 0 100 100 CP 12 Full supply mode Volume for return air OFF 0V energy hold off 0 100 0 10V or 2 10V OFF 0 100 OFF Signal limitation for VAV systems The m...

Reviews: