Display and operation 

 

Operation Modes 

STEP 

Normal mode 

The ventilation is operating based on selected values 

OFF 

Absence mode 

Ventilation is operated with on and off intervals. The intensity and 

duration of both on and off intervals may be defined with parameters. 

The default is 5.5 hours in off mode and 0.5 hours with minimum airflow.   

 

Party mode (FULL) 

Ventilation is fully activated. The reset time is shown on the display. It 

may be set.  

HIGH 

Full supply mode 

This mode is activated by an external input for example a switch on the 
kitchen or bathroom exhaust fan. The Supply air opens full and the 

return air is switched off. The values of full supply mode for both supply 

and return air are selectable through parameters.   

 

Time schedule mode 

Airflow is defined by time schedules 

 

Manual override 

Short term manual override of the time schedule value. After a fixed 

reset time of 60 min the positioner will revert to the scheduled value.  

Power Failure 

All the parameters and set points are memorized and do not need to be reentered. Depending on 

UP03

 the unit will 

remain switched off, switch on automatically or return to the operation mode it was in before the power failure. 

Deluxe version only

: Timer operation and daytime setting will be retained for 24h. The controller has to be connected to a 

power supply for at least 10 hours for the backup function to operate accordingly.  

 

 

 

Left (POWER) 

Turn unit ON or OFF. Text OFF 
displayed with current time.  
 
(Parameter setting: ESC key to 
leave menu option, cancel 
parameter change) 
 

Up  

Increment SET POINT  
(Parameter setting: SCROLL menu 
options and parameters) 
 

Down  

Decrement SET POINT  
(Parameter setting: SCROLL menu 
options and parameters) 
 

Contact indication 

Show when external contact close. 
(Parameter setting: All bars show when 
value can be changed) 
 

Mode 

Display of party, Auto or manual 

mode  

 
 

Large Digits 

Display of step, clock or parameter 
value. 

Vertical Bar:

 Fan speed or 

progress indication

 

Small Digits 

Display of set point, clock or 
parameter number. 

 

Right (PARTY)  

Toggle Party mode. In Party mode 
air volume is maximum. Reset time 
can be adjusted with up/down 
buttons.  
(Config mode: ENTER key to 
change parameter and confirm 
selection) 
 

Heat/Cool   

Press > 2 sec.: 
Toggle Heat / Cool / 
Fan only mode.  
 

Clock  

Press < 2 sec.: Enable / 
disable time schedules  
Press > 2 sec.: Change 
time and time schedules  
 

Summary of Contents for TCT-MZ

Page 1: ...plications Control of ventilation systems for comfort and industrial applications General description The TCT MZ is a microprocessor controlled precision positioner with real time clock and time sched...

Page 2: ...0 C 32 122 F 95 r H non condensing Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non...

Page 3: ...mmon U1 Analog output supply air 0 10 V DC U2 Analog output return air 0 10 V DC Mounting location On an easy accessible interior wall approx 1 5 m 4 5 above the floor in an area of average temperatur...

Page 4: ...are memorized and do not need to be reentered Depending on UP03 the unit will remain switched off switch on automatically or return to the operation mode it was in before the power failure Deluxe ver...

Page 5: ...schedules Press CLOCK key 2 sec Time schedule operation is enabled or disabled alternately Creating time schedules Step 1 Select a switching time Up to 8 Pr01 Pr08 Press CLOCK Key 2 sec SEL and curre...

Page 6: ...ct a password using UP or DOWN buttons Select 009 in order to get access to the user parameters Press OPTION after selecting the correct password 3 Once logged in the parameter is displayed immediatel...

Page 7: ...OFF 0V energy hold off 0 100 0 10V or 2 10V OFF 0 100 100 CP 12 Full supply mode Volume for return air OFF 0V energy hold off 0 100 0 10V or 2 10V OFF 0 100 OFF Signal limitation for VAV systems The m...

Reviews: