SRC-C1T1 - Indoor CO2+Temperature Transmitter 

The SRC-C1T1 is an indoor CO2 monitoring and temperature measuring 

transmitter. Three LEDs in the colors green, orange and red indicate the CO2 

concentration of the room air. This shows the user when to ventilate. The device 

has two analog outputs and one relay output. The CO2 background calibration of 

the SRC-C1T1 guarantees for accurate room air monitoring. 

Features 

 

Indoor CO2 and temperature measurement 

 

Indication with three separate color LEDs 

 

Minimum and maximum CO2 and temperature value memory 

 

Two analog output signals for CO2 and temperature values 

 

0…10

 

V or 2…10

 V measuring analog output signal selectable with 

jumpers 

 

Relay output indicating CO2 concentration 

 

Levels of CO2 indication programmable 

 

Automatic CO2 background calibration 

 

Output signal ranges programmable 

 

May be used as simple P-controller  

 

Averaging signal adjustable

 

 

Optional external display (OPA-S)

 

 

Status LED

 

Applications 

 

Indoor CO2 and temperature measurement 

(home, office, school, restaurant, greenhouse, …)

 

 

Recording of minimum and maximum CO2 and temperature limits for critical environments 

 

Direct control of extraction fan 

CO2 transmitter 

The CO2 concentration is measured through non-dispersive infrared (NDIR) waveguide technology with ABC automatic 

background calibration algorithm. The applied measuring technology guarantees excellent reliability and long-term 

stability. The microprocessor samples the CO2 once per second. It calculates an averaging signal over a preset number of 

samples and generates the output signal. 

The analog output signal range may be customized by jumpers and if required by a programming module. Standard signal 

ranges are 0

10 VDC and 2

10 VDC. Other ranges can be defined by using the external display and programming 

module (OPA-S). 

 

For OPA-

S usage see section 

Parameter configuration

 on pag

5. 

Automatic baseline calibration (ABC) 

The ABC background calibration constantly supervises the measured CO2 concentrations. The calibration function expects 

the CO2 values sink to 400 ppm when the room is not occupied. Over a period of several days the controller tries to reach 

this value step by step through recalibration of 30ppm per day max. In order to reach the given accuracy, it is required 

that the sensor is for at least 3 weeks in operation. 

 

NOTE: The ABC calibration works only in those applications where the CO2 concentration sinks regularly to fresh air 

levels of 400 ppm. For special applications such as green houses, animal farms, etc. the ABC calibration should be 

de-activated and the sensor should be manually calibrated. The automatic calibration can deactivate through the 

external operation terminal. The Sensor can be calibrated by the client and does not need to be sent in for 

calibration. 

For manual calibration see section 

Calibration

 on page 8. 

Temperature transmitter 

The temperature is measured with a precision sensing element. The microprocessor samples the temperature once per 

second. It calculates an averaging signal over a preset number of samples and generates an analog output signal based 

on a lower and an upper signal range value. Standard range is -

40…60°C (

-

40…140°F) and 10 seconds average. The 

measuring range and the averaging samples may be customized with the external display and programming module 

(OPA-S). 
The analog output signal range may be selected by jumpers and if required by a programming module. Standard signal 

ranges are: 0…10 VDC and 2…10 VDC. Other ranges can be defined by 

using the external display and programming 

module (OPA-S). 

 

For OPA-

S usage see section 

Parameter configuration

 on page

 5. 

 

 

 

Summary of Contents for 40-300198

Page 1: ...ers and if required by a programming module Standard signal ranges are 0 10 VDC and 2 10 VDC Other ranges can be defined by using the external display and programming module OPA S For OPA S usage see section Parameter configuration on page 5 Automatic baseline calibration ABC The ABC background calibration constantly supervises the measured CO2 concentrations The calibration function expects the C...

Page 2: ...ort applications It is not a safety device Where a device failure could endanger human life and property it is the responsibility of the client installer and system designer to add additional safety devices to prevent such a device failure Ignoring specifications and local regulations may cause equipment damage and endangers life and property Tampering with the device and misapplication will void ...

Page 3: ...pensation to stabilize after power up Signal outputs Analog outputs Output signal Resolution Maximum load DC 0 10 V or DC 2 10 V 10 bit 9 7 mV Voltage signal 1kΩ Relays output Insulation strength between relays and system electronics between neighboring contacts 48 VAC 1 A max 30 VDC 1 A max 500 VAC to EN 60 730 1 500 VAC to EN 60 730 1 Environment Operation Climatic conditions Temperature Humidit...

Page 4: ...ct exposure to sunlight o Do not install near heat sources e g radiators or other heat generating devices o Areas with poor air circulation and niches e g behind doors or shelves o Outside walls insufficiently insulated o In the direct influence area of ventilation openings and fans Mounting instruction See SRC C1T1 installation sheet no 70 000809 www vectorcontrols com Dimension mm inch 1 2 3 4 C...

Page 5: ...cified with output parameter OP 01 and OP 02 is left at the default value of 0 100 With any other setting the position of JP2 has no influence and the signal range defined with the output parameters applies For jumper location see section Wiring and Connection on page 4 Parameter configuration The transmitter can be adapted to fit perfectly into any application by adjusting the software parameters...

Page 6: ... calibration default 1 Calibrate to gas 0 ppm 2 Calibrate to fresh air 400 ppm 0 2 0 1 Sample interval 1 sec 2 Changing this parameter affects the control of the air quality LEDs or relay as follows Air quality LED Use of Parameters Green IP 08 value IP 10 value 400 2 Green Orange IP 10 value 400 2 IP 10 value Orange IP 10 value IP 10 value IP 11 value 2 Orange Red IP 10 value IP 11 value 2 IP 11 ...

Page 7: ...xecute 400 ppm calibration see section Calibration on page 8 If error cannot be removed by calibrating the sensor replace product Use the CO2 Transmitter as P Controller The CO2 transmitter may be converted into a proportional fresh air controller through a simple change of two parameter settings 1 Set a minimum concentration when the fresh air fan should start to run at its minimum speed for exam...

Page 8: ...tion Once the calibration has been executed the status LED will show constant RED and the green air quality led will blink for 10s if successful If calibration is not successful no stability of concentration for 5 min no communication with sensor the red air quality led will blink instead and the status LED will stay constantly on red in error mode Recalibrate or restart device to stop error mode ...

Page 9: ...SRC C1T1 CO2 TEMPERATUR TRANSMITTER MONITOR Doc 70 00 0794A V2 7 20210310 Vector Controls GmbH Switzerland Page 9 10 Subject to change without notice www vectorcontrols com Blank page ...

Page 10: ...V2 7 20210310 Vector Controls GmbH Switzerland Page 10 10 Subject to change without notice www vectorcontrols com Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls GmbH Switzerland info vectorcontrols com www vectorcontrols com ...

Reviews: