TCI-W13-U, TCI-W23-U Universal Controller 

O

UTPUT 

C

ONFIGURATION

 

 

Doc: 70-00-0414C, V2.0, 20220523  

© Vector Controls GmbH, Switzerland  

Page 15-22 

Subject to alteration 

Output configuration 

Analog output configuration (1A, 2A) 

Parameter  Description 

Range 

Default 

1A 00 

Select control loop or special function (0= OFF): 

1= LP1, 2= LP2 

3= Dehumidify (4 pipe, max LP1 cooling, LP2 direct) 

4= Manual positioning or by time schedule (0

100%) 

5= Transmit value of an input 

0

1A 01 

When 1A00 = 1configure output:

 

0= Heating/reverse  

1= Cooling/direct

 

2= Heating and cooling (2 pipe)

 

3= Transmit setpoint

 

When 1A00 = 4 Manual positioning or time schedule controlled 

0= time schedule only 

1= manual positioning and by time schedule 

When 1A00 = 5, select input (0= function disabled): 

1= 1T, 2= 1H,  3= 1U,  4= 2T

 

0

1A 02 

Type of output signal: OFF= 0

10V, 0

20mA,  ON= 2

10V, 4

20mA 

ON/OFF 

OFF 

1A 03 

Minimum limitation of output signal default and in loop heating mode 

0

100% 

1A 04 

Maximum limitation of output signal default and in loop heating mode 

0

100% 

100% 

1A 05 

Minimum limitation of output signal in loop cooling mode 

0

100% 

0% 

1A 06 

Maximum limitation of output signal in loop cooling mode  

0

100% 

100% 

1A 07 

Choose alarm to set output to 100% (output 0%on conflicting alarms) 

 

 



 

Alarm:   1 2 3 4 5 6 7 8 

ALA1

ALA8 



 

1A 08 

Choose alarm to set output to 0%. (output 0% on conflicting alarms) 

 

 



 

Alarm:   1 2 3 4 5 6 7 8 

ALA1

ALA8 



 

1A 09 

Transmit value (1A00=5): minimum input value 

per input 

0°C 

1A 10 

Transmit value (1A00=5): maximum input value 

per input 

100°C 

 

Set jumpers on the back of the controller: 0

10 VDC (default), or 0

20 mA. Further define analog outputs with 

A02.Custom ranges can be created by setting minimum and maximum signal limits. 

 

A control loop, special function, digital control or analog control sequence is not active until it is assigned an output.  

 

Low and high limit alarms are defined with input parameters. With output parameters assign an 

alarm to an output and select output state. The required output for each alarm can be 

individually selected. Multiple alarms can be signed to one output. If one alarm is selected to 

simultaneously activate and deactivate an output, the one to de-activate has precedence.  

 

With manual positioning (1A00=4) position the output by time schedule or directly in 0.5% 

steps. Setting 1A01 to 0 will disable manual positioning. The output will then only be controlled by time schedule.  

 

With dehumidifying (1A00=3) the maximum value is taken of cooling and dehumidifying. When the humidity is too 

high, cooling will continue to operate, even without a demand for cooling, to dehumidify the air and heating will 

activate to maintain comfort.  

 

Input values of inputs and set points of control loops may be transmitted on the analog outputs. 

 

Minimum or maximum limits of output signals may be reversed

. This allows to create a control option for 

example of 6-way valves where the following conditions are required: 0% full cooling, 50% no cooling or heating, 

100% full heating. This is achieved by setting 1A05 = 50%, 1A06 = 0%, 1A03 = 50% and 1A04 = 100%.  

While one sequence is reversed and the other is direct, the output will remain in OFF mode at the percentage defined 

with the last active minimum sequence.  

Note: Alarm values will not be affected by minimum or maximum limits.  

 

For 

VAV Function

 individual minimum and 

maximum limits may be assigned for cooling and 

heating. In VAV applications maximum cooling 

output matches the maximum air volume the 

VAV box is set to deliver. As demand for airflow 

in cooling mode decreases, airflow dwindles until 

it reaches minimum cooling output (1A05). This 

minimum will be based on the airflow needed at 

design cooling and is typically 10% to 15% of 

maximum cooling airflow. When this minimum is 

reached the system is in dead-band 

 neither 

heating nor cooling. Minimum airflow in heating 

mode is set with 1A03. As the system moves into heating mode, heating airflow increases until it reaches the 

maximum heating output (1A04), typically 30 to 50% of maximum cooling airflow.  

 

 

W

W

100 

 

50 

 

Y

H1

,Y

R1 

X

DZ

 

Y

C1,

Y

D1

 

Heating 

Cooling 

1A04

 

1A05

 

1A03

 

 1A06

 

T (°C/F), U(V, mA) 

Output Priority  

1. Alarm level low 
2. Alarm level high 

3. Operation mode OFF 
4. Control function 

Summary of Contents for 40-100267

Page 1: ...loops 8 time schedules 1 internal temperature sensor 1 universal input 1 passive input 1 binary PWM output 2 analog outputs Internal temperature sensor standard Add replaceable humidity element as req...

Page 2: ...ity Stability Capacity sensor 0 100 rH See Figure to the right 1 0 1 0 5 year Signal outputs Analog Output Output Signal Resolution Maximum Load DC 0 10 V 0 20 mA 9 76 mV 0 019 mA Voltage 1k Current 2...

Page 3: ...outputs Potential free relays contacts see technical specification UI Universal input NTC 10k 25 C 77 F 0 10 V or 0 20 mA selectable by jumper TI Passive input NTC 10 k 25 C 77 F or open contact AO A...

Page 4: ...r other heat sources e g the area above radiators and heat emitting equipment Avoid locations behind doors outside walls and below or above air discharge grills and diffusers Location of mounting is l...

Page 5: ...OFF displayed with current time W23 U temperature W13 U Parameter setting BACK to previous menu Menu navigation Back to previous home menu 6 OPTION C F Press 2 sec Enter set up CLOCK TCI W23 U SCHEDU...

Page 6: ...d each for 4 seconds on the large LCD digits in a continuous cycle while OFF is displayed in the small digits To prevent this make sure that in idle mode no input values are shown on either small or l...

Page 7: ...ec SEL and current time is displayed Press UP until SEL and H C is displayed Press RIGHT to toggle H or C SEL H C Display input values For TCI W13 Press OPTION 2 sec SEL and H C is displayed Press UP...

Page 8: ...ime from 00 00 23 45 15 minutes steps Press RIGHT to save switching time bar appears indicating step 1 complete DAY 1 blinks Pr01 08 00 Step 2 Apply selected switching time Pr01 to DAY1 Mon DAY 7 Sun...

Page 9: ...put configuration 1 analog output do1 do2 Binary output configuration 2 binary digital outputs relays FU Special functions Common to all TCI How to change parameters 1 Press UP DOWN buttons simultaneo...

Page 10: ...ON UP 09 Select type of content for large digits 00 OFF 0 5 1 01 Input 02 Setpoint 03 Analog Output 04 Binary Output 05 Clock UP 10 Select content source for large digits 0 OFF 0 4 1 Input 1 1T 2 1H...

Page 11: ...0 Match sensor range to input display With a differential pressure transmitter having 0 200 Pa measuring range set UO1 display minimum to 0 and U02 display maximum to 200 The allowable range value of...

Page 12: ...de setpoints There are two possibilities to change the setpoint in unoccupied economy mode Shift it by L07 or switch to the minimum setpoint limit in heating mode and maximum setpoint limit in cooling...

Page 13: ...is that the setpoint is normally not reached As the measured value gets closer to the setpoint the output reduces until it reaches a point a fraction above or below the setpoint where the output equal...

Page 14: ...l changeover when L23 OFF 0 255 min 5 min Cumulative stage action L16 0 is typically used in electric heat applications and single stage action L16 1 in fan speed applications Digital stage action L16...

Page 15: ...an be individually selected Multiple alarms can be signed to one output If one alarm is selected to simultaneously activate and deactivate an output the one to de activate has precedence With manual p...

Page 16: ...1 5 outputs disabled during switch on delay Delay is in seconds or minutes depending on d09 0 255 5 sec 1d 05 Activate PWM set cycle time seconds 0activates 0 deactivates 0 1650s 0s 1d 06 Choose alarm...

Page 17: ...larm to an output and select output state Each alarm s required output can be individually selected Multiple alarms can be signed to one output Should one alarm be simultaneously selected to activate...

Page 18: ...delay seconds 1275s 300s Fu 10 Input limit 1 per input 10 Fu 11 Input limit 2 Per input 90 Summer winter compensation changes the set point due to a change in an input value typically but not limited...

Page 19: ...han limit 2 ON When limit 2 is greater than limit 1enable when input value is between limit 1 and limit 2 When limit 2 is less than limit 1 enable when input value below limit 2 or above limit 1 ON OF...

Page 20: ...or temperature we recommend switching to cooling at 28 C 83 F and to heating at 16 C 61 F outdoor temperature These recommendations are given as suggestions The ideal settings may be different on the...

Page 21: ...TCI W13 U TCI W23 U Universal Controller Doc 70 00 0414C V2 0 20220523 Vector Controls GmbH Switzerland Page 21 22 Subject to alteration Empty page...

Page 22: ...oc 70 00 0414C V2 0 20220523 Vector Controls GmbH Switzerland Page 22 22 Subject to alteration Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls GmbH Switzerland info...

Reviews: