background image

 

TCI-W13-U, TCI-W23-U Universal Controller 

C

ONTROL LOOP 

C

ONFIGURATION

 

 

Doc: 70-00-0414C, V2.0, 20220523  

© Vector Controls GmbH, Switzerland  

Page 12-22 

Subject to alteration 

Control loop configuration 

Manipulation of the setpoint (1L and 2L) 

Parameter  Description 

Range 

Default 

1L 00 

Select loop control input (0= loop disabled): 

1= 1T,  2= 1H,  3= 1U,  4= 2T 

0

1L 01 

Minimum set point limit heating 

per input 

10°C(50°F) 

1L 02 

Maximum set point limit heating 

per input 

28°C(82°F) 

1L 03 

Minimum set point limit cooling 

per input 

18°C(64°F) 

1L 04 

Maximum set point limit cooling 

per input 

34°C(93°F) 

1L 05 

Enable set point compensation (0= disabled) 

1= winter compensation,  2= summer compensation,  3= winter and summer 

0

1L 06 

Loop input special (0= normal): 

1= combine loop 1 and loop 2   

2= cascade with reverse sequence of primary loop 
3= cascade with direct sequence primary loop 

4= cascade with both reverse and direct sequence of primary loop  

0

1L 07 

Unoccupied (economy) mode set point shift: (Function depends on 1L25) 

The occupied (comfort) setpoint is shifted by the value set with parameter. 

Reduces the heating set point and increases the cooling set point.  

per input 

5.0°C(10°F) 

1L 08 

Dead zone between heating and cooling set points 

The Dead Zone Span lies between the heating and the cooling setpoint. The 

output is off while the measured value is within the dead zone span. A 

negative dead zone is not possible. 

Per input 

1.0°(2°F) 

1L 25 

Fixed setpoint in Unoccupied (ECONOMY) mode  

OFF = Unoccupied (ECONOMY) set point shift applies 

ON = In Unoccupied (ECONOMY) mode use minimum setpoint limit as 

setpoint in heating mode or maximum setpoint limit in cooling mode 

ON, OFF 

OFF 

1L 26 

Setpoint compensation range, the maximum range the setpoint is shifted.  

0 = Temperature setback: the setpoint is shifted towards setpoint limit 

Acc input 

0.0°C 

1L 27 

Do not show current value in loop mode 

OFF = Current value is shown in loop mode in the large digits. The 

setpoint in the small ones.  

ON = Current value is not shown, the setpoint is shown in the large 

digits.  

ON, OFF 

OFF 

 

Unoccupied (economy) mode setpoints: There are two possibilities to change the setpoint in unoccupied (economy) 

mode: Shift it by L07 or switch to the minimum setpoint limit in heating mode and maximum setpoint limit in cooling.  

Unoccupied (economy) mode may be disabled by setting UP06 to OFF.  

 

Control loops and sequences are activated when output parameters are defined.  

 

Cascade control

 

In cascade control (L06) the setpoint of the secondary loop is determined by the demand of the primary loop. The 

setpoint of the secondary loop is calculated proportionally according to demand of the primary loop between minimum 

and maximum setpoint limits. Cascade control is activated by setting the parameter 

X

L06 of the secondary control 

loop. 
A typical application is a variable air volume system where the temperature output determines the pressure set point.  

Cascade Control Example 

 VAV Application 

Primary loop = temperature (1L) 

Secondary loop = airflow/pressure (2L) 

 

Settings: 2L01=20%,  2L02=60%,  2L06=2 

Depending on temperature 

setpoint, the demand is calculated 

for loop 1. For example 40%.  

Based on demand of loop 1, the setpoint of pressure loop is calculated 

proportionally between min (20%) and max (60%) pressure setpoint limits.  

A demand of 40% will result in a setpoint of 36% in the above example.  

 

Setpoint compensation

 

The setpoint compensation is typically used to compensate the set point due to a change in outside temperature. The 

relationship to the input used to drive the setpoint compensation is defined in auxiliary functions FU00 to FU07. 

 

Enable summer or winter set point compensation for this control loop with L05. Define the compensation range with 

L26.L26 defines the full setpoint shift once the compensation input has reached its lower limit in winter mode or 

upper limit in summer mode. 

Setting the range parameter to 0 will activate the setpoint setback function: The setback function shifts the set point 

toward the set point minimum or the set point maximum based on an external input value. Once the compensation 

input has reached its lower limit in winter mode or upper limit in summer mode, the setpoint is fixed to the setpoint 

minimum or maximum value. Commonly this is used for humidity control to avoid condensation on outside walls or 

windows in very cold weather.  

 

 

Summary of Contents for 40-100267

Page 1: ...loops 8 time schedules 1 internal temperature sensor 1 universal input 1 passive input 1 binary PWM output 2 analog outputs Internal temperature sensor standard Add replaceable humidity element as req...

Page 2: ...ity Stability Capacity sensor 0 100 rH See Figure to the right 1 0 1 0 5 year Signal outputs Analog Output Output Signal Resolution Maximum Load DC 0 10 V 0 20 mA 9 76 mV 0 019 mA Voltage 1k Current 2...

Page 3: ...outputs Potential free relays contacts see technical specification UI Universal input NTC 10k 25 C 77 F 0 10 V or 0 20 mA selectable by jumper TI Passive input NTC 10 k 25 C 77 F or open contact AO A...

Page 4: ...r other heat sources e g the area above radiators and heat emitting equipment Avoid locations behind doors outside walls and below or above air discharge grills and diffusers Location of mounting is l...

Page 5: ...OFF displayed with current time W23 U temperature W13 U Parameter setting BACK to previous menu Menu navigation Back to previous home menu 6 OPTION C F Press 2 sec Enter set up CLOCK TCI W23 U SCHEDU...

Page 6: ...d each for 4 seconds on the large LCD digits in a continuous cycle while OFF is displayed in the small digits To prevent this make sure that in idle mode no input values are shown on either small or l...

Page 7: ...ec SEL and current time is displayed Press UP until SEL and H C is displayed Press RIGHT to toggle H or C SEL H C Display input values For TCI W13 Press OPTION 2 sec SEL and H C is displayed Press UP...

Page 8: ...ime from 00 00 23 45 15 minutes steps Press RIGHT to save switching time bar appears indicating step 1 complete DAY 1 blinks Pr01 08 00 Step 2 Apply selected switching time Pr01 to DAY1 Mon DAY 7 Sun...

Page 9: ...put configuration 1 analog output do1 do2 Binary output configuration 2 binary digital outputs relays FU Special functions Common to all TCI How to change parameters 1 Press UP DOWN buttons simultaneo...

Page 10: ...ON UP 09 Select type of content for large digits 00 OFF 0 5 1 01 Input 02 Setpoint 03 Analog Output 04 Binary Output 05 Clock UP 10 Select content source for large digits 0 OFF 0 4 1 Input 1 1T 2 1H...

Page 11: ...0 Match sensor range to input display With a differential pressure transmitter having 0 200 Pa measuring range set UO1 display minimum to 0 and U02 display maximum to 200 The allowable range value of...

Page 12: ...de setpoints There are two possibilities to change the setpoint in unoccupied economy mode Shift it by L07 or switch to the minimum setpoint limit in heating mode and maximum setpoint limit in cooling...

Page 13: ...is that the setpoint is normally not reached As the measured value gets closer to the setpoint the output reduces until it reaches a point a fraction above or below the setpoint where the output equal...

Page 14: ...l changeover when L23 OFF 0 255 min 5 min Cumulative stage action L16 0 is typically used in electric heat applications and single stage action L16 1 in fan speed applications Digital stage action L16...

Page 15: ...an be individually selected Multiple alarms can be signed to one output If one alarm is selected to simultaneously activate and deactivate an output the one to de activate has precedence With manual p...

Page 16: ...1 5 outputs disabled during switch on delay Delay is in seconds or minutes depending on d09 0 255 5 sec 1d 05 Activate PWM set cycle time seconds 0activates 0 deactivates 0 1650s 0s 1d 06 Choose alarm...

Page 17: ...larm to an output and select output state Each alarm s required output can be individually selected Multiple alarms can be signed to one output Should one alarm be simultaneously selected to activate...

Page 18: ...delay seconds 1275s 300s Fu 10 Input limit 1 per input 10 Fu 11 Input limit 2 Per input 90 Summer winter compensation changes the set point due to a change in an input value typically but not limited...

Page 19: ...han limit 2 ON When limit 2 is greater than limit 1enable when input value is between limit 1 and limit 2 When limit 2 is less than limit 1 enable when input value below limit 2 or above limit 1 ON OF...

Page 20: ...or temperature we recommend switching to cooling at 28 C 83 F and to heating at 16 C 61 F outdoor temperature These recommendations are given as suggestions The ideal settings may be different on the...

Page 21: ...TCI W13 U TCI W23 U Universal Controller Doc 70 00 0414C V2 0 20220523 Vector Controls GmbH Switzerland Page 21 22 Subject to alteration Empty page...

Page 22: ...oc 70 00 0414C V2 0 20220523 Vector Controls GmbH Switzerland Page 22 22 Subject to alteration Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls GmbH Switzerland info...

Reviews: