5.5
Quick system and output configuration (application specific)
A set of predefined system and output parameters allows for easy selection of a typical TRA application.
With P000, it is possible to select from a set of predefined configurations.
Using a predefined configuration will override some of the affected P200, P201 and P203 parameters accordingly.
If one of the preset P200, P201 or P203 parameters is changed, P000 will be reset to 0.
Note: Changing P000 will affect the output assignment, depending on the chosen configuration. The position of valve and
fan may change. See 5.6.3, page 19.
Par/
Addr
Description
Data type / value
Default
R/
W
P000 Use a predefined application configuration
Range: 0…22
0
R/
W
5.5.1
Parameter P000 overview
The following predefined system configurations are available:
P000 value Description of predefined system configurations (application)
0
Default TRA application
1
2-pipe heating only, on/off valve, analog fan
2
2-pipe cooling only, on/off valve, analog fan
3
2-pipe manual heating or cooling, on/off valve, analog fan
4
2-pipe automatic heating or cooling, on/off valve, analog fan, changeover sensor at RT1
5
2-pipe heating only, modulating valve, 3 stage fan
6
2-pipe cooling only, modulating valve, 3 stage fan
7
2-pipe manual heating or cooling, modulating valve, 3 stage fan
8
2-pipe automatic heating or cooling, modulating valve, 3 stage fan, changeover sensor at RT1
9
2-pipe cooling only with electric heater, on/off valve, analog fan;
10
4-pipe manual heating or cooling, on/off valve, analog fan
11
4-pipe auto heating or cooling, on/off valve, analog fan, RT1 as digital changeover input (NO)
12
4-pipe heating and cooling, on/off valve, analog fan
13
Floor heating, on/off valve
14
Floor heating, modulating valve
15
Chilled ceiling, modulating valve
16
Chilled ceiling, on/off valve
17
Chilled ceiling, on/off valve, electric heater
18
Heated/chilled ceiling, on/off valve
19
Heated/chilled ceiling, modulating valve
20
4-pipe manual heating or cooling, 2 modulating valves, 3 stage fan
21
4-pipe auto heating or cooling, 2 modulating valves, 3 stage fan, RT1 as digital changeover input (NO)
22
2-pipe manual heating or cooling, modulating valve, analog fan
23
2-pipe manual heating or cooling, 3-point valve, analog fan
24
Chilled ceiling, modulating valve, electric heater
Depending on the desired functionality of the TRA control, additional configuration may be required.
A detailed description of the system and output configuration can be found in chapter 5.6 System and output
configuration, page 17.
5.5.2
Application modes: Wiring diagrams of outputs
An overview of the of the application specific output wiring diagrams can be found in chapter 5.6.3, page 19.