5.6.3
Application modes: Wiring diagrams of outputs
Affected Parameters
Parameter Description
Application mode
Enable electric heater
Valve type of heating/cooling system
P207
Number of fan speeds
P215
Number of fan speeds for analog fan
System
P000 predefined settings
P207, P215 settings
Wiring diagram of outputs
•
2-pipe system
•
on/off valve
•
DO1: Heating or cooling
•
AO1: 0-10V analog Fan
1 = Heating only
Analog fan
P200 0, 1, 2 or 3
P201 0 = OFF
2 = Cooling only
Analog fan
P203 0 = on/off valve
P207 4 = Analog fan
3 = Manual heating or cooling
Analog fan
4 = Automatic heating or cooling
Analog fan
P215 6 = 6 fan speeds (in
manual fan mode)
•
2-pipe system
•
Modulating valve
•
Heating or cooling
•
AO1: 0-10V modulating
valve
•
DO1-3: 3 stage fan
5 = Heating only
3-stage fan
P200 0, 1, 2 or 3
P201 0 = OFF
6 = Cooling only
3-stage fan
P203 2 = 0-10V Modulating
valve
P207 3 = 3 fan speeds
7 = Manual heating or cooling
3-stage fan
8 = Automatic heating or cooling
3-stage fan
•
2-pipe system cooling
only with electric heater
•
on/off cooling valve
•
DO1: Cooling
•
DO2: Electric Heater
•
AO1: 0-10V analog Fan
9 = Cooling with electric heater
Analog fan
P200 1 = Cooling only
P201 1 = ON = Electric
heater enabled
P203 0 = on/off valve
P207 4 = Analog fan
P215 6 = 6 fan speeds (in
manual fan mode)
•
4 pipe system
•
on/off valve
•
Heating and/or cooling
•
DO1: Cooling
•
DO2: Heating
•
AO1: 0-10V analog Fan
10 = Manual heating or cooling
3-stage fan
P200 4, 5 or 6
P201 0 = OFF
11 = Auto heating or cooling
RT1 as normally open DI
3-stage fan
P203 0 = on/off valve
P207 4 = Analog fan
12 = Heating and cooling
3-stage fan
P215 6 = 6 fan speeds (in
manual fan mode)
•
Floor heating system
•
on/off valve
•
DO1: Heating
13 = Floor heating
On/off valve
P200 7 or 9
P201 0 = OFF
18 = Heated/Chilled ceiling
On/off valve
P203 0 = on/off valve
P207 Any value