X2-O
PERATIONS
M
ANUAL
T
OUCH
D
ISPLAY
Doc: 70-07-0951A, 20220504
© Vector Controls LLC, USA
Page 12-18
Subjects to alteration
www.vectorcontrols.com
V
ECTOR
8.
Press the (
) button to select Monday (Day 1).
9.
Press the ( ) button to execute the program on Monday (Day 1).
➔
3 top bar symbols are displayed*.
10.
Press the ( ) button to
not
execute the program on Monday (Day 1).
➔
The 3 top bar symbols disappear*.
11.
Press the (
) button to go to the next day.
➔
DAY1
(Day 1) and
Pr01
(Program 1) is displayed in this example.
➔
3 bars indicate setting step 3 is executed.
* 3 top bar symbols are displayed for a set execution.
12.
Repeat this process to set
DAY2
to
DAY7
(Tuesday to Sunday).
13.
Set the action to be performed by pressing the ( ) ( ) and
(
) button depending on function selected in instruction No. 6:
a.
OP
(operating mode):
ON
= Occupied, normal operation
ECO
= Unoccupied, reduced operation
OFF
= protective operation
b.
LP
(control loop set point)
LP01
-
LP0x
*:
°C/°F
c.
AO
(analogue output position)
Ao01
-
Ao0x
**:
0
-
100%
d.
FAN
(fan control, fan speed)
FAN1
-
FAN2
:
fan speed 0-3 (
FSP0
-
FSP3
)
Auto mode (
Auto
)
e.
do
(digital output position)
do01
-
do0x
***:
ON
= enabled
OFF
= disabled
➔
4 and 5 bars indicate setting step 4 rep. 5 is executed.
* The number of available control loops depends on the used X2-controller.
** The number of available analogue outputs depends on the used X2-controller.
*** The number of available digital outputs depends on the used X2-controller.
OP
➔
14.
Press (
) to complete the setting of a timed event.
15.
Now you are back in menu "program selection" (instruction No. 4).
Start creating the next weekly schedules for program 2 to 12 as
required.