TLR-D5 Engineering Manual

 

Output Configuration 

General 

Two options are available: 3-point or binary.  

3-point output 

If 3-point is selected a 3-point actuator may be driven. The actuator has an open input and a close input. Applying 
power to the Open input will drive the valve or damper open, applying power to the close input will drive the valve or 

damper to the closed position.  
The running time of the actuator may be preset. We recommend to enter the maximum running time under maximum 

load in order to make sure that the valve can fully close and fully open in any circumstance.  
In order to open the valve or damper DO4 will be activated for the preset amount of time. After the expiration of the 

running time DO4 and DO5 will be OFF. The valve is closed by activating DO5 for the preset amount of time.  

Binary output 

Two devices may be controlled in case the 3-point actuator setting is OFF. DO4 will control a heating and DO5 a 
cooling device.  

Reversing Valve 

In binary output mode a reversing valve option is available. Select 1 if the reversing valve is to be activated while in 
heating mode, select 2 if the reversing valve is active while the unit is in cooling mode 

Configuration of controller 

Proceed in the following steps in order to adapt the controller to its application:  
 

1.

 

Connect power supply and inputs 

2.

 

Program input parameters (

IP

3.

 

Program control parameters (

1L

4.

 

Program output parameters (

OP

5.

 

Test function of unit 

6.

 

Switch off power 

7.

 

Connect outputs 

8.

 

Test controller 

9.

 

Set user settings (

UP

Configuration parameters for firmware version 2.2 

The TLR-D5 can be adapted to a wide variety of applications. The adaptation is done through parameters. The 
parameters can be changed on the unit without the need of additional equipment.  

Identifying the firmware version 

The parameters and functionality of controller depend on its firmware version and revision. It is therefore important to 
use a matching product version and parameter set. The Firmware version and revision version can be found when 
pressing simultaneously the 

S

 and 

T

 keys during several seconds. On the upper 7 segment display, the firmware 

version can be found, on the lower 7 segment display the current revision index (or “sub-version”).  

Accessing the control parameters 

Warning! Only experts should change these settings!  
 
The parameters can be changed as follows: 
 

1.

 

Press UP and DOWN button simultaneously for three seconds. The display will indicate the firmware version in 
the upper large digits and the revision in the lower small digits. Pressing the OPTION will show: CODE. 

2.

 

Select a password using UP or DOWN buttons. Dial 0241 in order to get access to the engineering parameters.  
Press OPTION after selecting the correct password.  

3.

 

Once logged in the parameter is displayed immediately 

4.

 

Select the parameters with the UP/DOWN keys. Change a parameter by pressing the OPTION key. The MIN 
and MAX symbols show up and indicate that the parameter may be modified now. Use UP and DOWN key to 
adjust the value. 

5.

 

After you are done, press OPTION or POWER in order to return to the parameter selection level.  

6.

 

Press the POWER key again so as to leave the menu and return to the group selection. Press POWER while in 
the group selection to return to normal operation.  

7.

 

The unit will return to normal operation if no key is pressed for more than 5 minutes. 

Doc: 70-00-0095 20081223 

©2008 Vector Controls 

Page 13 

SUNSTAR传感与控制 http://www.sensor-ic.com/ TEL:0755-83376549 FAX:0755-83376182 E-MAIL:[email protected]

SUNSTAR自动化 http://www.sensor-ic.com/ TEL: 0755-83376489 FAX:0755-83376182 E-MAIL:[email protected]

Summary of Contents for TLR-D5

Page 1: ...ree Celsius or Fahrenheit Deluxe Version o Clock and time schedule functions with special options for schools and universities o Clock keeps running for 48h in case of power failure o Display with blu...

Page 2: ...W1 40 11 00xx 1 Cooling only Accessories AER D5 24 40 11 0017 Base unit only 24V AER D5 230 40 11 0018 Base unit only 230V OPR 1 40 50 0001 2xAAA bat Remote controller S Tn10 2 SD Tn10 12 2 SD Tn10 20...

Page 3: ...ransport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing class 2M2 Standards conf...

Page 4: ...r if unclear Do not connect directly motors larger than 1kW Connection diagram Connection diagram Power supply L Power supply L Connection terminals Connection terminals RTEXT 0V AC N 2 1 FAN 1 3 Heat...

Page 5: ...not stand out more than 5 mm of the surface of the mounting plate 2 Connect the wires of the terminals to the communication wires according wiring diagram 3 Slide the two latches located on the top of...

Page 6: ...after a power failure Frost Protection The controller will enter frost protection mode if the room temperature drops below 5 C 41 F All heating outputs will be fully opened Frost protection mode will...

Page 7: ...nit is manually switched on while in scheduled off mode The unit will switch automatically off when the reset time defined in UP13 expires Setting UP13 to 0 disables the override reset A blinking cloc...

Page 8: ...e Pressing the OPTION button toggles Heating Cooling Fan only mode Access to Heat Cool change may be disabled with UP 03 Clock Setup and Time Schedule only available on Deluxe versions Clock Setup The...

Page 9: ...ivated in FAN ONLY mode Boost Pressing the boost button activates a 5 minute boost The output will be fully opened for the period of 5 minutes independent of demand Clock settings The remote controlle...

Page 10: ...he menu The unit will return to normal operation if no button is pressed for more than 5 minutes User Parameters Parameter Description Range Default UP 00 Enable access to operation modes ON OFF ON En...

Page 11: ...r the fan and heating or cooling stages by setting a minimum running time Delay OFF applies to all heating and cooling stages Delay ON Prevents a too short stopping cycle for fan and heating or coolin...

Page 12: ...cannot be overridden by using the terminal or time schedules Connecting the external temperature input to GND returns control of the operation mode to the terminal and time schedule This function may...

Page 13: ...s can be changed on the unit without the need of additional equipment Identifying the firmware version The parameters and functionality of controller depend on its firmware version and revision It is...

Page 14: ...r 3 point OFF Binary DO4 Heating DO5 Cooling ON 3 point output DO4 OPEN DO5 CLOSE ON OFF OFF FC 15 Reversing valve in binary mode 0 no reversing valve DO4 Heating DO5 Cooling 1 reversing valve while h...

Reviews: