background image

 

 

TLR-D5 Engineering Manual

 

Input configuration 

Input configuration 

Frost protection 

Frost protection 

Priority for alarm conditions 

1.

 

Frost protection 

2.

 

Operation mode OFF (EHO) 

3.

 

Comfort or Economy 

Frost protection will activate if the control temperature sinks below 5°C (41°F). 
Operation returns back to normal if the control temperature reaches 10°C (50°F). 
Frost protection alarm is displayed as FP in the smaller digits on the LCD display. An 
active alarm is indicated by a constant alarm display, once the alarm condition is 
removed, the alarm display flashes once per second until acknowledged by the 
OPTION key.  

Frost protection will activate if the control temperature sinks below 5°C (41°F). 
Operation returns back to normal if the control temperature reaches 10°C (50°F). 
Frost protection alarm is displayed as FP in the smaller digits on the LCD display. An 
active alarm is indicated by a constant alarm display, once the alarm condition is 
removed, the alarm display flashes once per second until acknowledged by the 
OPTION key.  
If frost protection is active, the unit will switch to high fan speed and set the analog output to full open.  

If frost protection is active, the unit will switch to high fan speed and set the analog output to full open.  
Frost protection should be disabled for cooling only systems. (Per default on TLR-D41-W01) 

Frost protection should be disabled for cooling only systems. (Per default on TLR-D41-W01) 

Temperature input 

Temperature input 

0.2

0.5

1.0

Accuracy in Kelvin, 
Temperature Input 

0 50  100

T °C 

The TLR-D5 includes an NTC-based passive temperature sensor. A 
sensor of the same type can be connected as alternative control input or 
as input for additional functions. The accuracy of the temperature input 
is shown in the table to the right. Specified accuracy can only be 
guaranteed by using a manufacturer approved temperature sensor. For 
best results use Sxx-Tn10 sensors.  

The TLR-D5 includes an NTC-based passive temperature sensor. A 
sensor of the same type can be connected as alternative control input or 
as input for additional functions. The accuracy of the temperature input 
is shown in the table to the right. Specified accuracy can only be 
guaranteed by using a manufacturer approved temperature sensor. For 
best results use Sxx-Tn10 sensors.  
Choose the active temperature input (intern or extern) for the controller 
input with 

FC17

. Setting 

FC17 

= 1 uses external input as control input. 

All other settings use internal sensor as control input 

Choose the active temperature input (intern or extern) for the controller 
input with 

FC17

. Setting 

FC17 

= 1 uses external input as control input. 

All other settings use internal sensor as control input 

T °C 

Additional functions of the external temperature input:  

Additional functions of the external temperature input:  

Following additional functions are available, in case the external temperature input is not used as control input.  

Following additional functions are available, in case the external temperature input is not used as control input.  
  

Toggle of Economy and 
comfort operation modes 

Toggle of Economy and 
comfort operation modes 

Economy and Comfort modes are controlled through an external contact by 
connecting the external temperature input to ground  

Economy and Comfort modes are controlled through an external contact by 
connecting the external temperature input to ground  

Activation Delay:

 Defines the delay the binary contact has to be open before 

Economy mode is activated. 

Activation Delay:

 Defines the delay the binary contact has to be open before 

Economy mode is activated. 
This function may be used together with key card switches for hotels or motion 
detectors for offices.  

This function may be used together with key card switches for hotels or motion 
detectors for offices.  

Remote enable 

Remote enable 

Opening the external temperature input will force the unit into the OFF operation 
mode. The operation mode cannot be overridden by using the terminal or time 
schedules. Connecting the external temperature input to GND returns control of the 
operation mode to the terminal and time schedule. This function may be used as 
window contact to prevent loss of energy.  

Opening the external temperature input will force the unit into the OFF operation 
mode. The operation mode cannot be overridden by using the terminal or time 
schedules. Connecting the external temperature input to GND returns control of the 
operation mode to the terminal and time schedule. This function may be used as 
window contact to prevent loss of energy.  

Heat-cool changeover with 
external switch 

Heat-cool changeover with 
external switch 

Control heat and cool setting of your controller from a central location by switching 
a contact to GND. Note: all ground levels of involved controllers must be the same. 
Choose if heat or cool is to be active when contact is open.  

Control heat and cool setting of your controller from a central location by switching 
a contact to GND. Note: all ground levels of involved controllers must be the same. 
Choose if heat or cool is to be active when contact is open.  

Auto Changeover with supply 
media temperature sensor 

Auto Changeover with supply 
media temperature sensor 

The external input may be used to automatically determine heating or cooling 
mode by measuring the temperature of the supply media. Connect a qualified 
passive sensor to the external input. Heating mode is activated once the supply 
temperature is above the heating limit. Cooling is activated when the supply 
temperature is below the cooling limit. The limits may be defined in software. 
Standard is 16°C (61°F) for cooling and 28°C (83°F) for heating 

The external input may be used to automatically determine heating or cooling 
mode by measuring the temperature of the supply media. Connect a qualified 
passive sensor to the external input. Heating mode is activated once the supply 
temperature is above the heating limit. Cooling is activated when the supply 
temperature is below the cooling limit. The limits may be defined in software. 
Standard is 16°C (61°F) for cooling and 28°C (83°F) for heating 

Auto Changeover with 
outside temperature sensor 

Auto Changeover with 
outside temperature sensor 

The external input may be used to automatically determine heating or cooling 
mode by measuring the outdoor temperature. Connect a qualified passive sensor to 
the external input. Heating mode is activated once the supply temperature is below 
the heating limit. Cooling is activated when the supply temperature is above the 
cooling limit. The limits may be defined in software. Standard is 16°C (61°F) for 
heating and 28°C (83°F) for cooling. 

The external input may be used to automatically determine heating or cooling 
mode by measuring the outdoor temperature. Connect a qualified passive sensor to 
the external input. Heating mode is activated once the supply temperature is below 
the heating limit. Cooling is activated when the supply temperature is above the 
cooling limit. The limits may be defined in software. Standard is 16°C (61°F) for 
heating and 28°C (83°F) for cooling. 

Key Card 

Key Card 

The external input is connected to a key card in hotels. If input is closed the unit is 
in normal operation with the setpoint being chosen by the end user. When input is 
opened, the unit will change to economy mode. A preset setpoint defined with 
FC12 for heating and FC13 for cooling is used instead of the selected setpoint.  The 
setpoint shift feature is disabled. 

The external input is connected to a key card in hotels. If input is closed the unit is 
in normal operation with the setpoint being chosen by the end user. When input is 
opened, the unit will change to economy mode. A preset setpoint defined with 
FC12 for heating and FC13 for cooling is used instead of the selected setpoint.  The 
setpoint shift feature is disabled. 

  

Doc: 70-00-0095 20081223 

©2008 Vector Controls 

Page 12 

SUNSTAR传感与控制 http://www.sensor-ic.com/ TEL:0755-83376549 FAX:0755-83376182 E-MAIL:[email protected]

SUNSTAR自动化 http://www.sensor-ic.com/ TEL: 0755-83376489 FAX:0755-83376182 E-MAIL:[email protected]

Summary of Contents for TLR-D5

Page 1: ...ree Celsius or Fahrenheit Deluxe Version o Clock and time schedule functions with special options for schools and universities o Clock keeps running for 48h in case of power failure o Display with blu...

Page 2: ...W1 40 11 00xx 1 Cooling only Accessories AER D5 24 40 11 0017 Base unit only 24V AER D5 230 40 11 0018 Base unit only 230V OPR 1 40 50 0001 2xAAA bat Remote controller S Tn10 2 SD Tn10 12 2 SD Tn10 20...

Page 3: ...ransport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing class 2M2 Standards conf...

Page 4: ...r if unclear Do not connect directly motors larger than 1kW Connection diagram Connection diagram Power supply L Power supply L Connection terminals Connection terminals RTEXT 0V AC N 2 1 FAN 1 3 Heat...

Page 5: ...not stand out more than 5 mm of the surface of the mounting plate 2 Connect the wires of the terminals to the communication wires according wiring diagram 3 Slide the two latches located on the top of...

Page 6: ...after a power failure Frost Protection The controller will enter frost protection mode if the room temperature drops below 5 C 41 F All heating outputs will be fully opened Frost protection mode will...

Page 7: ...nit is manually switched on while in scheduled off mode The unit will switch automatically off when the reset time defined in UP13 expires Setting UP13 to 0 disables the override reset A blinking cloc...

Page 8: ...e Pressing the OPTION button toggles Heating Cooling Fan only mode Access to Heat Cool change may be disabled with UP 03 Clock Setup and Time Schedule only available on Deluxe versions Clock Setup The...

Page 9: ...ivated in FAN ONLY mode Boost Pressing the boost button activates a 5 minute boost The output will be fully opened for the period of 5 minutes independent of demand Clock settings The remote controlle...

Page 10: ...he menu The unit will return to normal operation if no button is pressed for more than 5 minutes User Parameters Parameter Description Range Default UP 00 Enable access to operation modes ON OFF ON En...

Page 11: ...r the fan and heating or cooling stages by setting a minimum running time Delay OFF applies to all heating and cooling stages Delay ON Prevents a too short stopping cycle for fan and heating or coolin...

Page 12: ...cannot be overridden by using the terminal or time schedules Connecting the external temperature input to GND returns control of the operation mode to the terminal and time schedule This function may...

Page 13: ...s can be changed on the unit without the need of additional equipment Identifying the firmware version The parameters and functionality of controller depend on its firmware version and revision It is...

Page 14: ...r 3 point OFF Binary DO4 Heating DO5 Cooling ON 3 point output DO4 OPEN DO5 CLOSE ON OFF OFF FC 15 Reversing valve in binary mode 0 no reversing valve DO4 Heating DO5 Cooling 1 reversing valve while h...

Reviews: