TLR-D5 Engineering Manual

 

Doc: 70-00-0095 20081223 

©2008 Vector Controls 

Page 10 

Setting of parameters 

The TLR-D5 is an 

intelligent 

controller and can be adapted to fit perfectly into your application. The control operation is 

defined by parameters. The parameters are set during operation by using the standard operation terminal.  
The parameters are password protected. There are two levels of parameters: User operation parameters for access 
control settings and Expert parameters for control functions and unit setup. The passwords for user levels and expert 
levels are different. Only control experts should be given the control parameter password.  
 
The parameters can be changed as follows: 

1.

 

Press UP and DOWN button simultaneously for three seconds. The display shows the software version in the 

large digits and the software revision in the small digits.  

2.

 

Pressing the OPTION button will indicate CODE on the small digits and 000 on the large digits. 

3.

 

The code for accessing the user parameters is 009 

4.

 

Select this using UP or DOWN buttons. 

5.

 

Press OPTION button after selecting the correct code.  

6.

 

Once logged in, the parameter is displayed immediately. 

7.

 

Select the parameters with the UP/DOWN buttons. Change a parameter by pressing the OPTION button. The 

MIN and MAX symbols show up and indicate that the parameter may be modified now. Use UP or DOWN 
buttons to adjust the value. 

8.

 

After you are done, press OPTION or POWER in order to return to the parameter selection level.  

9.

 

Press the POWER button again so as to leave the menu. The unit will return to normal operation if no button 

is pressed for more than 5 minutes. 

User Parameters 

Parameter Description 

Range 

Default 

UP 00 

Enable access to operation modes 

ON, OFF 

ON (Enabled) 

UP 01 

Enable access to set points 

ON, OFF 

ON (Enabled) 

UP 02 

Enable manual control of fan speeds 

ON, OFF 

ON (Enabled) 

UP 03 

Enable change of heating / cooling mode for 2 pipe systems 

ON, OFF 

W00: ON 
(Enabled) 
W01: OFF 
(Disabled) 

UP 04 

Enable access to time programs: 

ON, OFF 

ON (Enabled) 

UP 05 

State after power failure:  
0 = off, 1 = on, 2 = state before power failure 

0, 1, 2 

UP 06 

Enable Economy functionality 

ON, OFF 

ON (Economy ) 

UP 07 

Celsius or Fahrenheit, ON for Fahrenheit, OFF for Celsius 

ON, OFF 

OFF (Celsius) 

UP 08 

Calibration value of temperature sensor. If required it is possible 
to shift the temperature –10° to +10° in 0.1K steps.  

-10…10 

UP 09 

Enable frost protection 

ON, OFF 

W00 = ON  

(Frost 

Protection) 

W01 = OFF 

(No Frost 

Protection) 

UP 10 

Select contents of Large LCD display in standard mode: 

0…5 

00 = OFF 
01 = Setpoint 
02 = Temperature Input of control loop  
03 = Output Fan Speed 
04 = Clock 

05 = Alternate Temperature Sensor 

UP 11 

Select contents of small LCD display in standard mode 

0…5 

4, 1 

UP 12 

Deluxe only 

Clock display type:  
OFF  = Show 24hour clock 
ON   = Show 12hour clock (AM, PM) 

ON, OFF 

OFF (24h) 

UP 13 

Deluxe only 

Reset timer for override mode: Only available for deluxe version 

= Reset of override mode is not active.  

1…255 = delay in minutes to switch off device if ON/Economy mode is 

activated while the unit is scheduled to be in OFF mode 

0…255 60 

(Min) 

 
 
 

 

Subject to alteration 

SUNSTAR传感与控制 http://www.sensor-ic.com/ TEL:0755-83376549 FAX:0755-83376182 E-MAIL:[email protected]

SUNSTAR自动化 http://www.sensor-ic.com/ TEL: 0755-83376489 FAX:0755-83376182 E-MAIL:[email protected]

Summary of Contents for TLR-D5

Page 1: ...ree Celsius or Fahrenheit Deluxe Version o Clock and time schedule functions with special options for schools and universities o Clock keeps running for 48h in case of power failure o Display with blu...

Page 2: ...W1 40 11 00xx 1 Cooling only Accessories AER D5 24 40 11 0017 Base unit only 24V AER D5 230 40 11 0018 Base unit only 230V OPR 1 40 50 0001 2xAAA bat Remote controller S Tn10 2 SD Tn10 12 2 SD Tn10 20...

Page 3: ...ransport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing class 2M2 Standards conf...

Page 4: ...r if unclear Do not connect directly motors larger than 1kW Connection diagram Connection diagram Power supply L Power supply L Connection terminals Connection terminals RTEXT 0V AC N 2 1 FAN 1 3 Heat...

Page 5: ...not stand out more than 5 mm of the surface of the mounting plate 2 Connect the wires of the terminals to the communication wires according wiring diagram 3 Slide the two latches located on the top of...

Page 6: ...after a power failure Frost Protection The controller will enter frost protection mode if the room temperature drops below 5 C 41 F All heating outputs will be fully opened Frost protection mode will...

Page 7: ...nit is manually switched on while in scheduled off mode The unit will switch automatically off when the reset time defined in UP13 expires Setting UP13 to 0 disables the override reset A blinking cloc...

Page 8: ...e Pressing the OPTION button toggles Heating Cooling Fan only mode Access to Heat Cool change may be disabled with UP 03 Clock Setup and Time Schedule only available on Deluxe versions Clock Setup The...

Page 9: ...ivated in FAN ONLY mode Boost Pressing the boost button activates a 5 minute boost The output will be fully opened for the period of 5 minutes independent of demand Clock settings The remote controlle...

Page 10: ...he menu The unit will return to normal operation if no button is pressed for more than 5 minutes User Parameters Parameter Description Range Default UP 00 Enable access to operation modes ON OFF ON En...

Page 11: ...r the fan and heating or cooling stages by setting a minimum running time Delay OFF applies to all heating and cooling stages Delay ON Prevents a too short stopping cycle for fan and heating or coolin...

Page 12: ...cannot be overridden by using the terminal or time schedules Connecting the external temperature input to GND returns control of the operation mode to the terminal and time schedule This function may...

Page 13: ...s can be changed on the unit without the need of additional equipment Identifying the firmware version The parameters and functionality of controller depend on its firmware version and revision It is...

Page 14: ...r 3 point OFF Binary DO4 Heating DO5 Cooling ON 3 point output DO4 OPEN DO5 CLOSE ON OFF OFF FC 15 Reversing valve in binary mode 0 no reversing valve DO4 Heating DO5 Cooling 1 reversing valve while h...

Reviews: